Chart 3.2

Natural Gas Consumption

*Assumes an average heating value of 1050 BTU/SCF and a Specific Gravity of 0.60.

Chart 3.3

Propane Gas Consumption

*Assumes an average heating value of 2500 BTU/SCF and a Specific Gravity of 1.53.

Chart 3.4 allows for a 0.3 inch W.C. pressure drop in the supply pressure from the building main to the
inlet of the unit. Refer to the chart for the appropriate range of inlet pressures for each gas type. When
sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3 inch
W.C. pressure drop has been subtracted from the main pressure. If the 0.3 inch W.C. pressure drop is
too high, refer to NFPA 54 or the Gas Engineer’s Handbook for other gas pipe capacities.

3.0

Installation

Gas Supply Installation Instructions

Model

Manifold

Pressure

(Inches W.C.)

Min. Inlet
Pressure

(Inches W.C.)

Max. Inlet

Pressure

(Inches W.C.)

Gas

Consumption

(CFH)*

Gallons

per hour

*

Orifice

Size

Number of

Orifices

FA-100P

10.0

11.0

14.0

40.0

1.10

54 DMS

4

FA-125P

10.0

11.0

14.0

50.0

1.37

54 DMS

5

FA-150P

10.0

11.0

14.0

60.0

1.65

54 DMS

6

FA-175P

10.0

11.0

14.0

70.0

1.92

54 DMS

7

FA-200P

10.0

11.0

14.0

80.0

2.20

1.45mm

7

FA-225P

10.0

11.0

14.0

90.0

2.47

54 DMS

9

FA-250P

10.0

11.0

14.0

100.0

2.75

1.45mm

9

Model

Manifold

Pressure

(Inches W.C.)

Min. Inlet
Pressure

(Inches W.C.)

Max. Inlet

Pressure

(Inches W.C.)

Gas

Consumption

(CFH)*

Orifice

Size

Number

of Orifices

FA-100N

3.5

5.0

14.0

95.2

42 DMS

4

FA-125N

3.5

5.0

14.0

119.0

42 DMS

5

FA-150N

3.5

5.0

14.0

142.9

42 DMS

6

FA-175N

3.5

5.0

14.0

166.7

42 DMS

7

FA-200N

3.5

5.0

14.0

190.5

39 DMS

7

FA-225N

3.5

5.0

14.0

214.3

42 DMS

9

FA-250N

3.5

5.0

14.0

238.1

40 DMS

9