beautypg.com

0 troubleshooting guide – Detroit Radiant Products Company FA Series User Manual

Page 42

background image

42

FA

Series

4.0

Troubleshooting Guide

4.0

Troubleshooting Guide

Turn on control

device for heat.

Does the draft

inducer motor

turn on?

No

Yes

Limit switch is open or pressure

switch is stuck closed. Find

faulty switch and repair.

Does the

pressure switch

indicator light

turn on?

Yes

Does the circuit

board send

spark to the

electrode?

Yes

Does the valve

indicator light

turn on?

Yes

Continued on page 44.

Does the air circulating

fan turn on immediately?

Does the heater have 120 VAC

at the main power connection?

Find source of

electrical problem.

No

No

Yes

Yes

Is the inlet or outlet of the

heater obstructed, or is

the vent exceeding the

recommended lengths?

No

Check for loose wiring or

restrictions in the hose

connection to the pressure

switch. Are they acceptable?

Remove obstruction or

correct vent lengths.

No

Does the electrode

appear to be

physically damaged?

Temporarily disconnect the igniter wire

from the circuit board and check for

continuity. Is there continuity?

Replace igniter.

Yes

No

Does the gas valve

turn on? Do you see

the burners in the

sight glass?

Replace wire.

Replace circuit

board.

Yes

No

Gas valve

indicator light is

burned out.

Replace light.

Yes

Check inlet pressure to the heater. Is

it within the minimum and maximum

allowable range as per the rating plate?

No

Adjust inlet

pressure.

No

Yes

Are the wires to and from the

gas valve properly connected?

No

Yes

No

Yes

Does the gas

valve turn on?

No

Yes

Yes

Correct wiring.

No

Replace wiring or hose

connections.

No