Micromod MOD: Modcell 2050R MODBUS Communications User Manual
Page 55
IB-23C650M
CONTROLLER ATTRIBUTE LISTING - REGISTER DATA
More Computer Activity Data (registers)
Reg.
#
Description
Register Value
2050R
Displayed Value
113
R W
Manual control mode status display
mnemonic with computer active.
Default display is MAN. Each
character is configurable; this register
defines the first character (M in the
default MAN).
ASCII code for first
character in status
display
Letter M (default) or
letters A-Z,
numbers 0-9 plus
other special
characters per
configuration. See
RS-485 Setup
Menu.
114
R W
Same as display described in Reg.
#113. This register defines the
second and third characters (A and N
in the default MAN)
.
ASCII code for
second and third
characters in status
display
Letters A and N
(default) or letters
A-Z, numbers 0-9
plus other special
characters per
configuration. See
RS-485 Setup
Menu.
115
R W
Local 2 set-point status display
mnemonic with computer active.
Default display is LO2. Each
character is configurable; this register
defines the first character (L in the
default LO2).
Same as Reg. #113
Letter L (default) or
other configured
character. See Reg.
#113.
116
R W
Same as display described in Reg.
#115. This register defines the
second and third characters (O and 2
in the default LO2).
Same as Reg. #114
Letter O & #2
(default) or other
configured
characters. See
Reg. #114.
117
R W
Local 3 set-point status display
mnemonic with computer active.
Default display is LO3. Each
character is configurable; this register
defines the first character (L in the
default LO3).
Same as Reg. #113
Letter L (default) or
other configured
character. See Reg.
#113.
118
R W
Same as display described in Reg.
#117. This register defines the
second and third characters (O and 3
in the default LO3)
Same as Reg. #114
Letter O & #3
(default) or other
configured
characters. See
Reg. #114.
Note:
The "computer active" references in this section mean "when the
computer activity timer is enabled".
51