CONTROLLER ATTRIBUTE LISTING - REGISTER DATA

Alarm Data (registers)

Reg.

#

Description

Register Value

2050R

Displayed Value

70

R W

Alarm 1 trip point

• Process High or Low

Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3

• Deviation High or Low

Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3

• Output High or Low

• Input 2 High or low

-2995 to 30000
-2995 to 30000
-2995 to 30000
-2995 to 30000

1 to 30000
1 to 30000
1 to 30000
1 to 30000

0 to 1000

Same as Process
high or low

-2995 to 30000

-299.5 to 3000.0
-29.95 to 300.00
-2.995 to 30.000

1 to 30000

0.1 to 3000.0

0.01 to 300.00

0.001 to 30.000

0.0 to 100.0

Same as Process
high or low

71

R W

Alarm 2 trip point

Same as Reg. # 70

Same as Reg. #70

72

R W

Alarm 3 trip point

Same as Reg. # 70

Same as Reg. #70

73

R W

Alarm 4 trip point

Same as Reg. # 70

Same as Reg. #70