beautypg.com

Micromod MOD: Modcell 2050R MODBUS Communications User Manual

Page 52

background image

IB-23C650M

CONTROLLER ATTRIBUTE LISTING - REGISTER DATA

Computer Activity Data (registers) Cont’d

Reg.

#

Description

Register Value

2050R

Displayed Value

80

R W

Computer active: set-point mode value

0 to 255

0 to 255

81

R W

Computer fail: control mode

0
1
2

Last

Manual

Auto

82

R W

Computer fail: output value

0 to 1000

0.0 to 100.0%

83

R W

Computer fail: output 2 value

0 to 1000

0.0 to 100.0%

84

R W

Computer fail: relay A

0
1
2

Last

Off
On

85

R W

Computer fail, relay B

Same as Reg. #84

Same as Reg. #84

86

R W

Computer fail: relay C

Same as Reg. #84

Same as Reg. #84

87

R W

Computer fail: set-point mode

0
1
2
3
4
5

Last

LOC

LO2
LO3
LO4

REM

88

R W

Computer fail: set-point value

Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3

-3000 to 30000
-3000 to 30000
-3000 to 30000
-3000 to 30000

-3000 to 30000
-300.0 to 3000.0
-30.00 to 300.00
-3.000 to 30.000

See register #113 through #131 for

more computer activity data

48