beautypg.com

Micromod MOD: Modcell 2050R MODBUS Communications User Manual

Page 44

background image

IB-23C650M

CONTROLLER ATTRIBUTE LISTING - REGISTER DATA

Common Data (registers) Cont’d

Reg.

#

Description

Register Value

2050R

Displayed Value

7

R _

Field Input 1

Register #9, Bits 1 & 0 = 0
Register #9, Bits 1 & 0= 1
Register #9, Bits 1 & 0= 2
Register.#9, Bits 1 & 0 = 3

Note: This register permits reading of
actual process input to 2050R when
Coil #14 is TRUE. Data is copied to
Reg. #10 when Coil #14 is FALSE.

-32000 to +32000
-32000 to +32000
-32000 to +32000
-32000 to +32000

-32000 to +32000

-3200.0 to +3200.0
-320.00 to +320.00
-32.000 to +32.000

Values are not

displayed when Coil

#14 is TRUE. See

Reg. #10

8

R _

Field Input 2

Note: This register permits reading of
actual input 2 to 2050R when Coil
#15 is TRUE. Data is copied to Reg.
#11 when Coil #15 is FALSE.

Same as Reg. #7

Same as Reg. #7
values

Values are not

displayed when Coil

#15 is TRUE. See

Reg. #11.

9

Bits

15 - 4

R _

Bits 15 - 4 indicate active process
alarms (PA) and diagnostics (DIAG).
See Register #6 for bit descriptions.

Bits

1 & 0

R _

Process decimal point. Positions the
decimal point in the process and set-
points engineering displays.

0
1
2
3

n

n.n

n.nn

n.nnn

10

R W

Process Variable for Display

• Coil #14 is FALSE:

Actual 2050R Process variable
(field input 1) is displayed

• Coil #14 is TRUE:

Display value is written from host

Same as Reg. #7

values

Same as Reg. #7

values

Same as Reg. #7

values

Same as Reg. #7

values

11

R W

Active set-point variable

Register No. 9, Bits 1 & 0 = 0
Register No. 9, Bits 1 & 0 = 1
Register No. 9, Bits 1 & 0 = 2
Register No. 9, Bits 1 & 0 = 3

-3000 to 30000
-3000 to 30000
-3000 to 30000
-3000 to 30000

-3000 to 30000

-300.0 to 3000.0
-30.00 to 300.00
-3.000 to 30.000

12

R W

Control analog output value.

-80 to 1100

-8.0 to 110.0

13

R W

Input No. 2
• Coil # 15 is FALSE:

Input No. 2 value is obtained
from Field Input 2

• Coil #15 is TRUE:

Input No. 2 value is written from
host

Same as Reg. #7

values

Same as Reg. #7

values

Same as Reg. #7

values

Same as Reg. #7

values

40