beautypg.com

Micromod MOD: Modcell 2050R MODBUS Communications User Manual

Page 49

background image

IB-23C650M

CONTROLLER ATTRIBUTE LISTING - REGISTER DATA

Tuning Parameter Data (registers) Cont’d

Reg.

#

Description

Register Value

2050R

Displayed Value

55

R W

Gain or heat gain value

1 to 30000

0.1 to 3000.0

56

R W

Reset or heat reset

10 to 12000

0.01 to 120.00
repeats/minute

57

R W

Preact value

0 to 30000

0.0 to 3000.0
seconds derivative
response

58

R W

Manual reset value

0 to 1000

0.0 to 100.0%

59

R W

Remote set-point ratio or AMRB ratio

-30000 to 30000

-300.00to 300.00

60

R W

Remote set-point bias or AMRB bias

Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3

-30000 to 300000
-30000 to 300000
-30000 to 300000
-30000 to 300000

-3000 to 30000

-300.0 to 3000.0
-30.00 to 300.00
-3.000 to 30.000

61

R W

Time proportioning cycle time or heat
cycle time

10 to 3000

1.0 to 300.0 sec.

62

R W

On/off differential gap

Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3

0 to 1000
0 to 1000
0 to 1000
0 to 1000

0 to 100

0.0 to 10.0

0.00 to 1.00

0.000 to 0.100

63

R W

Heat/cool output crossover

1 to 3000

0.1 to 300.0%

64

R W

Crossover output off hysteresis

0 to 250

0.0 to 25.0 in %

output centered on

crossover value

(±25%)

65

R W

Cool gain value

1 to 30000

0.1 to 3000.0

66

R W

Cool reset value

10 to 1200

0.1 to 120.0

repeats/minute

67

R W

Cool cycle time value

10 to 3000

1.0 to 300.0 sec.

68

R W

Position proportioning deadband value

0 to 500

0.0 to 50.0%

69

R W

Position proportioning preact value

0 to 500

0.0 to 50.0%

45