Electrical installation - wiring, Frequency single phase, Current sinking* wiring (models 29x-6xx) – Max Machinery 243 Helical Flow Meter User Manual
Page 15: Frequency quadrature, Wiring frequency
Max Machinery, Inc.
© Copyright 2013
Rev. 002Q4
15
Frequency
Single Phase
Wiring
All Other
Models
Mating Cable
Wire Color
Turck
Pin #
Case Ground
Case
Blue
3
Common
Com
Black
4
Power 5-26 Vdc
V+
Brown
1
Pulse Output
Ph A
White
2
N/A
NC
Grey
5
Frequency
Single Phase
* A current sinking device produces an output pulse which is the opposite of a sourcing device.
A positive DC voltage must be applied to the wire running between PhA and your PLC. When the
output is triggered, this voltage will be grounded to zero volts. Note: use a 5k ohms resistor to limit
the current flow in the signal line.
Current Sinking* Wiring
(models 29X-6XX)
PLC
Digital
Input
V+
V+
Out
0V
Transmitter
Turck Pin #2
All Other Models
Mating Cable
Wire Color
Turck
Pin #
Case Ground
Case
Blue
3
Common
Com
Black
4
Power 5-26 Vdc
V+
Brown
1
Output Phase A
Ph A
White
2
Output Phase B
Ph B
Grey
5
Frequency
Quadrature
Turck Connector
2
1
4
5
3
Electrical Installation - Wiring
Wiring FREQUENCY
The electrical connector versions are pre-wired inside the transmitter and ready to accept a mating cable (available from
the factory). The liquid-tight, NPT models need to be wired during installation as shown in the table below:
Wiring
The 6-pin connector version is pre-wired inside the transmitter and is ready to accept a mating cable (available from the
factory). The Liquid-Tight and NPT models need to be wired during installation as shown in the table below:
NPT Models
6-Pin Connector
Circuit Board
Terminal #
Mating Cable
Wire Color
Pin #
Case Ground
1
Green
A
Common
2
Black
B
Power (+5-24 VDC)
3
Red
C
Pulse Output
4
White
D
Electrical Installation - Wiring
280 Series Transmitters