CALIBRATION FOR RATE
With each flow transmitter there will be a calibration sheet that will supply the average pulses per volume
of specific units. Using the formulas below calculate the KFR value to enter into the display.
KFR VALUE CALCULATIONS FOR RATE
Gallons per Minute:
6000 / Average K-Factor in Pulses per Gallon
Liters per Minute:
6000 / (Average K-Factor in Pulses per cc X 1000)
Pounds per Minute:
6000 / (Average K-Factor in Pulses per Gallon / (Specific Gravity X 8.35)
Kilograms per Minute:
6000 / (Average K-Factor in Pulses per cc X 1000) / Specific Gravity
ENTERING THE KFR FACTOR FOR RATES
1. Cycle display using the MODE button, until the
RATE A
is displayed.
2. Press and hold the ENT button until the display enters program mode. At this point you should
see
KFR A VALUE
, with a number underneath it. The first digit should be blinking.
3. Using the UP or DN and SEL buttons adjust the
KFR A VALUE
to figures calculated from
above.
4. Press ENT
to accept
KFR A VALUE
setting. This will then move to the next screen.
5. Press ENT
to accept
SAMPLE A
setting.
6. Note: Do not adjust the SAMPLE A SETTING!
7. Press ENT
to accept
ENG UNITS A
setting.
8. Note: Do not adjust the SAMPLE A SETTING!
9. Calibration for
RATE A
is now complete.