DISPLAY PROGRAMMING
(cont)
TOTAL A B
No programming necessary.
STATUS ONE
No programming necessary.
WARNINGS
Although you can program alarms from here it is recommended that the alarms be programmed
from the
RATIO A B
setup.
RATE A
Cycle display using the MODE button, until the
RATE A
is displayed.
Press SEL until the decimal point is blinking. Using the UP or DN button, move the decimal until
3 decimal places are set. Then, using the SEL and UP and DN buttons, set the
KFR A
VALUE
to the appropriate value. At this point .500 should be used.
The KFR A VALUE
will
be set in the Calibration section.
Press ENT
to accept
KFR A VALUE
setting. This will then move to the next screen.
Press ENT
to accept
SAMPLE A
setting (Leave at 10). This will then move to the next screen.
Set the
ENG UNITS A
display by using the UP or DN and SEL buttons. Either set to KG/M,
GR/M, LBS/M or OZ/M
Note: Remember what measurement was setup to display. This is the measurement that needs to be used
during the calibration process.
Press ENT
to accept
ENG UNITS A
setting. This will return you to the
RATE A
display
RATE B
Cycle display using the MODE button, until the
RATE B
is displayed.
Press SEL until the decimal point is blinking. Using the UP or DN button, move the decimal until
3 decimal places are set. Then, using the SEL and UP and DN buttons, set the
KFR B
VALUE
to the appropriate value. At this point .500 should be used.
The KFR B VALUE
will
be set in the Calibration section.
Press ENT
to accept
KFR B VALUE
setting. This will then move to the next screen.
Press ENT
to accept
SAMPLE B
setting (Leave at 10). This will then move to the next screen.
Set the
ENG UNITS B
display by using the UP or DN and SEL buttons. Either set to KG/M,
GR/M, LBS/M or OZ/M
Note: Remember what measurement was setup to display. This is the measurement that needs to be used
during the calibration process.
Press ENT
to accept
ENG UNITS B
setting. This will return you to the
RATE B
display