Liquid Controls IT300N-BBL User Manual
Page 7
6
DEFINITIONS
(continued)
r deCloC
: (ratemeter decimal location) Sets the decimal location for the ratemeter. The
ratemeter decimal is not a dummy decimal and will scale the rate display accordingly. (i.e. if
the r decloc is set in the tenths position (123.4), 100 will be displayed as 100.0). The
ratemeter decimal location is restricted to a maximum of 4 places (.1234). However, the
number of ratemeter decimal locations allowable is reduced with each decimal place added
to the factor decimal. Press the
←
key to move the decimal. Press the E key to enter the
displayed decimal location.
Note: The flow rate indicator will flash “59999” if the computed flow rate exceeds the 59999
display capability of the indicator. Choose a new decimal point location to avoid this.
oUt lo
: (out low) Sets the low setting for the 4-20 mA analog output. Key in the low rate value at
which the unit will output 4mA. Press the
↑
key to increment each digit. Press the
←
key to
step to the next digit to the left. Press the E key to enter the displayed out lo value.
oUt HI
: (out high) Sets the high setting for the 4-20 mA analog output. Key in the high rate value
at which the unit will output 20 mA. Press the
↑
key to increment each digit. Press the
←
key
to step to the next digit to the left. Press the E key to enter the displayed out hi value.
pUlseoUt
: (pulse out divider) This allows the unit to output a pulse for each least significant total
count divided by the selected divider. The pulse out can be divided by 1 (
d 1
), 10 (
d 10
), 100
(
d 100
), or turned off (
off
). With the divider set at 1, the unit will give a pulse out for every
increment of the LSD displayed.
Note: For maximum battery life, turn the pulse output off when pulse output is not used.
Selecting the proper pulse output divider may be needed so that the pulse output
does not exceed the maximum rate of the pulse output (10 Hz). If the pulse output
pulses too quickly a flashing display will result. Pressing the “M” key will result in a
display of an error message “E PULSE”. Press the “E” key to return to the run mode.
FrEQ.OUT
: (pulse out frequency) Sets the pulse output frequency / duration. Selections are: 1, 2,
4 or 8 Hz. This menu item is skipped if
pUlseoUt
is turned off.
loC Code
: (lock code) Sets the 4 digit lock code to be entered when the unit prompts
ent Code
.
This allows the user to gain access to the menu when the unit is locked. Press the
↑
key to
increment each digit. Press the
←
key to step to the next digit to the left. Press the E key to
enter the displayed code.
Record this number for later use!
loC UnIt
: (lock unit) Sets the panel lock ON or OFF. Press the
↑
key to select On or OFF. Press
the E key to enter the displayed selection.