DEFINITIONS
ent Code
: (enter code) This prompt will only appear if the panel lock is ON. Press the
↑
key to
increment each digit. Press the
←
key to step to the next digit to the left. Press the E key to
enter the 4 digit code. If the entered code is correct, the display will advance to the next
menu prompt (CLr tot). If incorrect, the display will return to the run mode.
Clr tot
: (clear total) Clears (resets) the totalizer. Press the E key to clear the total and return to
the run mode. Press the M key to skip and advance to the next menu selection.
FAC nnUl
: (factor multiplier) Sets the factor multiplier value. Press the
↑
key to select
1
,
10
,
100
,
1000
. Press the E key to enter the displayed value.
fdeC
: (factor decimal) Sets the decimal location for the factor. This location is restricted to 3
places (59.999). The use of this decimal automatically limits the number of decimal locations
allowable in the rate and total to acceptable ranges. Press the
←
key to move the decimal.
Press the E key to select the displayed decimal location.
faC
lInear
/
10poInt
: (factor type) This prompt will only appear if the unit is ordered with the 10 point
linearization option. The
10 poInt
linearization selection is recommended for flow meters
whose K-factors change with different flow rates. This selection allows users to enter up to
10 different frequencies with 10 corresponding K-factors for different flow rates. The
lInear
setting is used for flow meters whose output is linear over its' entire operating flow range.
Press the
↑
key to step to the desired choice. Press the E key to enter the displayed factor
type.
No
/
yes
set10pt
: (set 10 point?) This prompt allows the user to skip the 10 point setup routine.
Select
yes
for initial setup or to change the present 10 point values. Select
No
to skip and
keep the existing values.
faC
: (factor) This prompt appears on all units with linear inputs. The Factor is the number of
pulses per unit volume for the flow sensor. The pulses/unit volume is implied by the totalizer
descriptor when a descriptor is used. The implied units for the Factor are then as follows:
GAL
pulses/gallon
LIT
pulses/liter
FT3
pulses/ft3
M3
pulses/M3
Factors from 0.001 to 59999 may be used. A 0 value for the factor is not allowed and a
warning message will be given. The factor is displayed on the subsidiary (lower) display.
Press the
↑
key to increment each digit. Press the
←
key to step to the next digit to the left.
Press the E key to enter the displayed factor.