5

DEFINITIONS

(continued)

fr#

: (frequency for point #) This prompt will only appear when 10 point selected. It sets the

frequency for each of the 10 points (#). Press the

key to increment each digit. Press the

key to step to the next digit to the left. Press the E key to enter the desired frequency for
point #.

faC#

: (factor for point #) This prompt will only appear when 10 point selected. It sets the factor

for each of the 10 points (#). Press the

key to increment each digit. Press the

key to

step to the next digit to the left. Press the E key to enter the desired factor for point #.

NOTE:

The display will advance to the next point (Fr#) after each entry of the Fr & Fac until all 10 points are
complete. entering a 0 in the Fr or fac setting will advance the display to the next menu prompt (tdec).

tdeC

: (totalizer decimal) Sets the decimal location for the totalizer. The totalizer decimal is not

a dummy decimal and will scale the totalizer display accordingly. (i.e. if the tdec is set in the
tenths position (1234567.8), 100 will be displayed as 100.0). The location of the decimal
point allows for greater resolution of both the totalizer display and the pulse output. The
pulse output advances at a rate dependent on the least significant digit of the totalizer. The
totalizer decimal location is restricted to a maximum of 4 places (1234.5678). However, the
number of totalizer decimal locations allowable is reduced with each decimal place added to
the factor decimal. Press the

key to move the decimal. Press the E key to enter the

displayed decimal location.
Note:

The selection of the factor decimal point limits the available selections
for the number of decimal points available for the totalizer. This is automatic.

Enter your selection of the Factor’s decimal point before entering the totalizer
decimal point to assure the proper selection of the totalizer decimal point has
been made.

tot desC

: (totalizer descriptor) This allows you to illuminate one of the available descriptors on

the display (GAL, LIT, FT3, M3 or "blank"). Press the

key to select the descriptor. Press

the E key to enter the selected descriptor.

sCale

: (ratemeter scaling) Sets the rate readout. Choose rate per hour (

Hrs

), minutes (

nnIn

) or

seconds (

seC

). The scale setting is shown on the main (upper) display. Press the

key to

step to the desired choice. Press the E key to enter the displayed scale setting.
Note: A rate descriptor corresponding to the above choice will be illuminated on the display.