Example – Liquid Controls IT375 User Manual
Page 16
Sponsler, Inc.
Model IT375
Example Pg. 16
5. EXAMPLE
A typical 2 inch liquid flowmeter has an operating range of 15 – 225 gpm and produces 148.914 pulses per gallon with a
maximum output frequency of 563Hz. 3 points of linearization is required. The flow rate is displayed in gallons/min
with 1 decimal point and the total in liters with no decimals. A 4-20mA output is installed and 4mA is to represent 15
gallons/min and 20mA is to represent 225 gallons/min The instrument is then programmed as follows:
Calibration mode is entered by removing the lower cover strip (ie. the dark grey strip along the bottom of the enclosure)
and reversing it’s left right orientation.
The following values are then entered:
Step
Value of
Parameter
Description
CAL00
0
No Pulse Output
CAL01
000148
Kfactor (whole numbers)
CAL02
914
Kfactor (decimals)
CAL03
0.25
Cutoff Frequency
CAL04
1
Rate decimal position
CAL05
1
Timebase
CAL06
01
Filter disabled
CAL07
0
Total decimal position
CAL08
000000
Total Conversion (whole numbers)
CAL09
264201
Total Conversion (decimals) (1/3.785)
CAL10
000015
Low Alarm (whole numbers)
CAL11
0000
Low Alarm (decimals)
CAL12
000225
High Alarm (whole numbers)
CAL13
000
High Alarm (decimals)
CAL14
000015
4mA Output (whole numbers)
CAL15
0000
4mA Output (decimals)
CAL16
000225
20mA Output (whole numbers)
CAL17
000
20mA Output (decimals)
CAL18
3
3 point linearization
INP 01
000037
Point #01 frequency (whole numbers)
INP.01
0746
Point #01 frequency (decimals)
OUT 01
000148
Point #01 Kfactor (whole numbers)
OUT.01
085
Point #01 Kfactor (decimals)
INP 02
000268
Point #02 frequency (whole numbers)
INP.02
338
Point #02 frequency (decimals)
OUT 02
000148
Point #02 Kfactor (whole numbers)
OUT.02
073
Point #02 Kfactor (decimals)
INP 03
000563
Point #03 frequency (whole numbers)
INP.03
061
Point #03 frequency (decimals)
OUT 03
000148
Point #03 Kfactor (whole numbers)
OUT.03
080
Point #03 Kfactor (decimals)
SOFT
202d3.2L
Software Version