Liquid Controls IT375 User Manual
Page 13
Sponsler, Inc.
Model IT375
Programming Pg. 13
Step
Comment
CAL 10 & 11 program the flow rate below which the low
alarm relay will close. The value can be programmed in the
range 0 to 999,999.
CAL 12
High Alarm or Pulse Output Factor - whole numbers.
CAL 13
High Alarm or Pulse Output Factor - digits after the decimal
point.
CAL 12 & 13 program the flow rate above which the high
alarm relay will close. The value can be programmed in the
range 0 to 999,999.
If the scaled pulse output is selected (CAL0 = 1), then the
value will represent the total per pulse, eg. 5 liters per pulse.
CAL 14
4mA Setpoint- whole numbers.
CAL 15
4mA Setpoint- digits after the decimal point.
CAL 14 to CAL 15 represent the flow rate at which 4mA will
be output. If the 4-20mA output is not installed, these
parameters can be ignored.
CAL 16
20mA Setpoint- whole numbers.
CAL 17
20mA Setpoint- digits after the decimal point.
CAL 16 & 17 represent the flow rate at which 20mA will be
output. If the 4-20mA output is not installed, these parameters
can be ignored.
CAL 18
Number of linearization points.
00 = linearizer disabled
xx = number of points
INP 01
Point #1 Frequency – whole numbers.
Input points must be programmed in ascending frequency
order
INP.01
Point #1 Frequency – digits after the decicmal
OUT 01
Point #1 Kfactor – whole numbers.
Kfactors can never be zero
OUT.01
Point #1 Kfactor – digits after the decimal.
SOFT
Software Version.