CSB Battery TPL121500A User Manual
Powered by

F.V/Time
15MIN 30MIN 60MIN 90MIN 2HR
3HR
4HR
5HR
6HR
7HR
8HR
10HR 20HR
1.67V
278
177
104
76.4
60.2
44.3
35.7
29.6
25.3
22.0
19.5
15.9
8.34
1.70V
263
170
100
74.3
59.5
43.9
35.3
29.3
24.9
21.8
19.1
15.8
8.25
1.75V
238
158
95.5
72.1
57.9
42.7
34.2
28.1
24.0
21.0
18.8
15.4
8.06
1.80V
211
146
90.2
68.1
55.6
41.3
32.6
27.2
23.4
20.3
18.1
15.0
7.88
1.83V
195
138
85.0
65.2
53.3
39.8
31.7
26.4
22.8
19.8
17.5
14.4
7.69
1.85V
184
133
82.9
63.7
52.1
38.9
31.0
25.8
22.2
19.4
17.3
14.3
7.50
1.90V
158
118
77.2
62.6
48.1
35.4
28.1
23.4
20.0
17.6
15.8
13.0
6.94
F.V/Time
15MIN 30MIN 60MIN 90MIN 2HR
3HR
4HR
5HR
6HR
7HR
8HR
10HR 20HR
1.67V
2,954 1,909 1,135
843
669
497
402
334
286
249
221
180
94.7
1.70V
2,821 1,855 1,122
833
667
496
400
333
284
248
218
179
94.4
1.75V
2,575 1,747 1,084
824
666
489
394
324
277
243
217
178
93.4
1.80V
2,322 1,627 1,033
785
646
480
380
318
274
238
212
175
92.5
1.83V
2,164 1,545 1,002
768
628
467
372
311
268
233
207
170
90.9
1.85V
2,057 1,495
977
753
618
459
367
305
263
230
204
169
89.2
1.90V
1,812 1,370
909
693
572
423
337
281
240
212
189
157
83.5
Terminal Hardware Initial Torque
ABS(UL94-V0) & (UL94-HB) / L.O.I higher than 28
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
TPL 121500A
12V 150Ah
TPL 121500A is a front terminal battery up to 12 years
expected life under normal float charge As with all CSB
batteries, all are rechargeable, highly efficient, leak proof
and maintenance free.
Cells Per Unit
6
Voltage Per Unit
12
Capacity
150Ah @ 8hr-rate to 1.75V per cell @25 (77 )
Weight
Approx. 53.6kg(118.17 lbs)
Maximum Discharge Current
800A(5sec)
Internal Resistance
Approx. 6.5 m
Operating Temperature Range
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Nominal Operating Temperature Range
25
3 (77
5 )
Float Charging Voltage
Recommended Maximum Charging Current Limit 45A
Equalization / Cycle Use Charging Voltage
Terminal
Container Material
Specification
2.275 0.025V / Cell at 25
(77 ) Temp.
Coefficient 3.3mV/ ( 1.8mV/ )
0.05mV/ ( 1.8mV/ )
2.45V Temps coefficient
I2-Thread lead alloy recessed terminal to accept M6 bolt
Powered by
Width (W)
Dimensions :
Unit: mm (inch)
)
L
(
h
t
g
n
e
L
)
H
(
t
h
g
i
e
H
l
l
a
r
e
v
O
323.0±2.5 (12.72±0.10)
547.0±2.5 (21.54±0.10)
125.6±1.5 (4.94±0.06)
120-in-lbs.(13.58 N-m)
CSB-manufactured
VRLA
batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
RA1403
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.