CSB Battery HR1290W User Manual
Hr 1290w, 12v 90w, Powered by
Cells Per Unit
6
Voltage Per Unit
12
Capacity
90W @ 15min-rate to 1.67V per cell @25 (77 )
Weight
Approx.
6.80 kg(14.99 lbs)
Maximum Discharge Current
300A(5sec)
Internal Resistance
Approx. 9.5m
Operating Temperature Range
Nominal Operating Temperature Range
25
3 (77
5 )
Float Charging Voltage
13.5 to 13.8 VDC/unit Average at 25 (77 )
Recommended Maximum Charging
9A
Current Limit
Equalization and Cycle Service
14.4 to 15.0 VDC/unit Average at 25 (77 )
Self Discharge
CSB Batteries can be stored for more than 6 months at
25 (77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
I1-Thread lead alloy recessed terminal to accept M5 bolt
Container Material
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
HR 1290W
12V 90W
Specification
Powered by
HR 1290W is specially designed for high efficient
discharge application. Its characteristics are high energy
density, small footprint and high discharge efficiency. It can
be used for more than 260 cycles at 100% discharge in cycle
service, up to 5 years in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H)
Container height (h)
Length (L)
167.0±2.0 (6.57±0.08)
--
181.0±2.0 (7.12±0.08)
76.2±1.0 (3.00±0.04)
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
177
124
95.8
79.4
68
48.7
38.4
27.3
15.8
11.5
1.67V
156
114
90.2
77.6
65.2
48.4
38.1
27
15.7
11.4
1.70V
147
109
87.8
76.4
63.9
47.6
37.7
26.9
15.6
11.3
1.75V
131
102
82.9
72.8
61.1
46.2
37
26.3
15.5
11.2
1.80V
115
92.5
77.2
67.7
58
44
35.5
25.5
15.2
11.1
1.85V
98.6
82.9
70.8
60.8
53.3
40.7
32.6
23.8
14.5
10.6
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
1701
1282
1041
868
753
544
429
309
183
133
1.67V
1570
1193
989
850
734
540
428
307
182
132
1.70V
1509
1155
962
838
726
534
426
305
181
131
1.75V
1398
1087
913
802
704
520
416
300
179
130
1.80V
1282
1011
862
756
665
501
402
295
177
129
1.85V
1166
926
797
687
608
461
375
277
168
124
CSB-manufactured
VRLA
batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.