CSB Battery HR12120W User Manual
Powered by
Cells Per Unit
6
Voltage Per Unit
12
Capacity
120 W @ 15min-rate to 1.67V per cell @25 (77 )
Weight
Approx.
10.2 kg(22.49 lbs)
Maximum Discharge Current
225A(5sec)
Internal Resistance
Approx. 9 m
Operating Temperature Range
Nominal Operating Temperature Range
25
3 (77
5 )
Float Charging Voltage
13.5 to 13.8 VDC/unit Average at 25 (77 )
Recommended Maximum Charging
12A
Current Limit
Equalization and Cycle Service
14.4 to 15.0 VDC/unit Average at 25 (77 )
Self Discharge
CSB Batteries can be stored for more than 6 months at
25 (77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
I1-Thread lead alloy recessed terminal to accept M5 bolt
Container Material
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
HR 12120W
12V 120W
Specification
Powered by
HR 12120W is specially designed for high efficient
discharge application. Its characteristics are high energy
density, small footprint and high discharge efficiency. It can
be used for more than 260 cycles at 100% discharge in cycle
service, up to 5 years in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H)
Container height (h)
Length (L)
175.0±2.0 (6.90±0.08)
--
166.0±2.0 (6.54±0.08)
125.0±1.5 (4.93±0.06)
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
169
148
125
107
94.2
70.5
56.1
41.2
24.5
16.8
1.67V
153
135
115
100
88.9
67.0
53.6
39.7
24.0
16.6
1.70V
146
128
109
95.5
85.6
65.3
52.5
39.2
23.7
16.4
1.75V
132
117
101
88.9
80.2
62.0
50.4
37.8
23.1
16.2
1.80V
117
105
91.2
81.3
73.3
58.3
48.0
36.0
22.2
15.8
1.85V
100
92.5
82.4
74.3
67.3
54.3
45.7
34.6
21.2
15.2
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
1,745
1,622
1,419
1,199
1,030
771
621
462
284
197
1.67V
1,608
1,495
1,315
1,119
975
738
600
453
279
194
1.70V
1,539
1,427
1,260
1,084
947
724
590
447
276
193
1.75V
1,412
1,306
1,161
1,012
895
701
578
435
270
190
1.80V
1,273
1,181
1,060
944
853
676
561
418
263
186
1.85V
1,100
1,045
966
877
805
648
536
402
253
181
CSB-manufactured
VRLA
batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
A
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.