CSB Battery TPL121350A User Manual
Powered by
F.V/Time
15MIN 30MIN 60MIN 90MIN 2HR
3HR
4HR
5HR
6HR
7HR
8HR
10HR 20HR
1.67V
250
159
93.2
68.1
54.2
39.9
32.1
26.7
22.8
19.8
17.6
14.3
7.51
1.70V
236
153
91.0
66.7
53.6
39.5
31.7
26.3
22.4
19.6
17.2
14.2
7.43
1.75V
213
144
87.2
64.7
52.7
38.4
30.8
25.3
21.6
18.9
16.9
13.8
7.26
1.80V
189
132
82.3
62.2
51.3
37.2
29.4
24.5
21.1
18.3
16.3
13.5
7.09
1.83V
174
125
79.1
60.7
49.9
35.9
28.5
23.8
20.5
17.8
15.8
13.0
6.92
1.85V
164
119
76.4
59.2
48.7
35.0
27.9
23.2
20.0
17.5
15.5
12.8
6.75
1.90V
142
106
69.4
56.4
43.3
31.9
25.3
21.1
18.0
15.9
14.2
11.7
6.24
F.V/Time
15MIN 30MIN 60MIN 90MIN 2HR
3HR
4HR
5HR
6HR
7HR
8HR
10HR 20HR
1.67V
2,658 1,718 1,022
751
602
447
362
301
257
224
198
162
85.2
1.70V
2,544 1,672
996
739
601
446
360
299
256
223
196
161
84.9
1.75V
2,339 1,586
958
716
587
440
354
292
249
218
195
160
84.1
1.80V
2,095 1,488
927
699
574
432
342
286
247
214
191
157
83.2
1.83V
1,954 1,387
893
684
561
420
335
280
242
210
186
153
81.8
1.85V
1,857 1,343
871
668
545
410
330
275
237
207
184
152
80.3
1.90V
1,631 1,233
818
628
515
381
303
253
216
190
170
141
75.2
Terminal Hardware Initial Torque
ABS(UL94-V0) & (UL94-HB) / L.O.I higher than 28
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
TPL 121350A
12V
135Ah
TPL 121350A is a front terminal battery up to 12 years
expected life under normal float charge As with all CSB
batteries, all are rechargeable, highly efficient, leak proof
and maintenance free.
Cells Per Unit
6
Voltage Per Unit
12
Capacity
135Ah @ 8hr-rate to 1.75V per cell @25 (77 )
Weight
Approx. 53.6kg(118.17 lbs)
Maximum Discharge Current
800A(5sec)
Internal Resistance
Approx. 6.5 m
Operating Temperature Range
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Nominal Operating Temperature Range
25
3 (77
5 )
Float Charging Voltage
Recommended Maximum Charging Current Limit 40.5A
Equalization / Cycle Use Charging Voltage
Terminal
Container Material
Specification
2.275 0.025V / Cell at 25
(77 ) Temp.
Coefficient 3.3mV/ ( 1.8mV/ )
0.05mV/ ( 1.8mV/ )
2.45V Temps coefficient
I2-Thread lead alloy recessed terminal to accept M6 bolt
Powered by
Width (W)
Dimensions :
Unit: mm (inch)
)
L
(
h
t
g
n
e
L
)
H
(
t
h
g
i
e
H
l
l
a
r
e
v
O
323 .0±2.5 (12.72±0.10)
547.0±2.5 (21.54±0.10)
125.6±1.5 (4.94±0.06)
120-in-lbs.(13.58 N-m)
CSB-manufactured
VRLA
batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
RA1403
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.