CSB Battery HRL12330W User Manual
Powered by

Polypropylene(UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
13.5 to 13.8 VDC/unit Average at 25 (77 )
14.4 to 15.0 VDC/unit Average at 25 (77 )
Cells per unit
Voltage per unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
6
12
330 W@15min-rate to 1.67V per cell @25
o
C(77
o
F)
Approx.29.6 kg(65.26 lbs)
800A(5sec)
Approx. 4
m
25
o
C±3
o
C (77
o
F±5
o
F)
33A
CSB Batteries can be stored for more than 6 months at
25
o
C (77
o
F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
HRL 12330W
12V 330W
Specification
Powered by
HRL 12330W is specially designed for high efficient discharge
application. Its characteristics are high energy density, small
footprint and high discharge efficiency. It can be used for more
than 260 cycles at 100% discharge in cycle service, up to 10
years in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H)
Container height (h)
Length (L)
214.3±2.5 (8.44±0.10)
211.3±2.5 (8.32±0.10) 308.7±2.5 (12.15±0.10) 169.0±2.0 (6.66±0.08)
F.V/Time
5MIN
10MIN
15MIN
20MIN
30MIN
40MIN
45MIN
50MIN
60MIN
90MIN
1.60V
383
260
201
165
123
98.4
89.9
82.0
70.2
52.1
1.67V
339
239
188
157
117
94.2
85.3
78.1
67.1
49.4
1.70V
318
229
181
152
113
91.1
83.4
76.4
64.9
47.3
1.75V
284
210
168
144
106
85.6
78.9
72.5
61.2
44.4
1.80V
253
193
158
135
98.4
79.6
72.5
66.4
56.6
41.6
1.85V
219
177
147
125
92.5
74.9
68.5
62.5
53.5
39.5
F.V/Time
5MIN
10MIN
15MIN
20MIN
30MIN
40MIN
45MIN
50MIN
60MIN
90MIN
1.60V
4,044
2,772
2,148
1,770
1,320
1,062
972
888
762
566
1.67V
3,621
2,608
2,040
1,712
1,290
1,032
936
864
744
547
1.70V
3,438
2,520
1,979
1,679
1,266
1,008
924
852
726
529
1.75V
3,115
2,354
1,891
1,605
1,210
963
894
816
696
503
1.80V
2,791
2,180
1,795
1,528
1,145
918
833
762
650
484
1.85V
2,478
2,016
1,690
1,428
1,070
864
786
720
613
460
CSB-manufactured
VRLA
batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.