English – Burkert Type TAT002 User Manual
Page 8
6 - 0911
english
ENTER PROGRAMMING LEVEL
Hold down the SET1 +
button for at least 3
seconds.
Select with
Pr2 and then confirm with the SET1
button.
Enter the password 321 and then confirm with the
SET1 button.
Enter the „3“ and then 1 x SET1 button
Enter the „2“, and then 1 x the SET1 button
Enter the „2“, and then 1 x the SET1 button
You are now in the Parameter List.
USER LEVEL PR1
Hold down the SET1 +
button for at least 3
seconds. PR1 contains all the parameters that can
be accessed by the user. The device shows the first
parameter that is available in the user level.
SERVICE LEVEL PR2 (PASSWORD 321)
See:
Accessing the programming level
ADDING/REMOVING PARAMETERS IN THE USER LEVEL PR1
Accessing the programming level
The status can be changed with the SET1 +
buttons.
If a parameter is not visible in the PR1 level, this will
be indicated by an LED point.
CHANGING SET-VALUE 1 / SET-VALUE 2
Hold down the SET button for 2 seconds.
Change the set-value within 10 s with the
or
buttons.
You can save the new set-value by briefly pressing
the SET button or by waiting 10 seconds.