english
Alarms
tbA
Status of the control relay
oFF = Relay deactivated
after acknowledgement
on = Relay activated
(any button) in any
alarms ituation
AS
Configuration of the alarm
cL = Terminal 5-6 closed
relay at an alarm
oP = Terminal 5-6 closed
Measured value display
LCI
Lower analog
Lower display value at current input
Display value
4 mA or at voltage input 0 V
(-1999...1999)
(only for the inputs 0-20 mA, 0-1V,
0-10 V)
UCI
Upper analog
Upper display value at current input
display value
20 mA or at voltage input 1 V or 10 V
(-1999...1999)
(only for the inputs 0-20 mA, 0-1V,
0-10 V)
rES
Resolution
Selecting display resolution
in = integer (-99...+199)
dEC = 1 decimal point (-99.0...199.0)
cE = 2 digits after the decimal point
(-99.00...199.00)
1,2
irE = large measuring range
(-999...1999)
1,2
UdM
Units
Display of the units directly in the
illuminated display. Regardless of which
controller type is being used:
see
General description
PbC
Type of sensor
Type of inout
Temperature sensor U):
J = Thermoelement „J“; Pt = Pt100;
C = Thermoelement „K“; Ptc = PTC;
S = Thermoelement „S“; ntc = NTC
Current / voltage input
cur = 4...20 mA; 0-1 = 0...1 V;
(AU)
10 = 0...10 V
1
Only for devices with an input of 4...20 mA or 0...1 V or 0...10 V
2
Only for current or voltage input
ATTENTION!
If rES is changed at a later time, the following parameters must
be checked::
SET, Hy1, LS1, uS1, ALL, ALu, ALH, LCi, uCi, LAo, uAo, HES
NOTE
Selecting a decimal point is not possible for thermocouples.