PID control (only Output 1 at Ft = PID)
Pb
Proportional range
Preset possibility only for Set-value 1
(°C or °F)
which affects the first control output.
This value determines the bandwidth
(on both sides of the set-value) that
exist within the proportional control.
int
integral action time
Determines the integral behaviour of the
(0...999 sec)
controller. The greater the deviation,
the higher the effect.
dEt
Derivative action time
Determines the differential behaviour of
(0...999 sec)
the controller. The greater the deviation,
the higher the effect.
Sr
Measurement rate
Time between 2 consecutive
(1...10 sec)
following measurements for the
calculation of dt. A smaller value
increases the response time.
rS
Manual Reset
With this parameter, the proporti-
(°C or °F)
onal control deviation can be moved up /
down.
The value will be defined as the
same amount, but in the opposite
direction to the deviation detected.
A r
Integralband
Range (on both sides of the set-value)
(°C oder °F)
within which the integral action time is
effective. The higher the value,
the greater the effect.
Cyt
Zykluszeit
Minimum time during which the out-
(1...500 sec)
put relay is switched on and off.
drb
Soft-start band
If the temperature is outside the band
(°C oder °F)
(on both sides of the set-value), a new
Soft-Start will be initiated.
(0 = deactivated)
dSi
Dynamic set-value
This value determines the stepwise
control (°C or °F)
set-value increase from SET1.
(0 = deactivated)
dSt
Clock time for dynamic
clock time for dynamic set-value-
set-value cpntrol
control with regard to dSi (SOFT-Start).
(1...999 sec)
NOTE
You can access hidden parameters by holding down the
buttons SET + for 3 seconds in the programming level HY.
The message Pr2 appears.