English, 3technical data – Burkert Type TAT002 User Manual
Page 18
16 - 0911
english
3
TECHNICAL DATA
• Housing
ABS, self-extinguishing
• Dimensions
Front 74 x 32 mm, Depth 60 mm
• Assembly
Panel-mounting unit for 29 x 71 mm cutout
• Protection class
IP65 from front, only with front seal RG-C
IP20
• Connections
Screw terminals
• Pipe cross-section
≤2.5 mm
2
• Auxiliary energy
depending on model
12...24 V AC/DC; ±10%
230 V AC; ±10%; 50/60 Hz
optional 110 V AC; ±10%; 50/60 Hz
• Power consumption
max. 3 VA
• Display
three digits, red LED, height 12 mm
• Inputs
configurable NTC / PTC or
NTC / PTC / Pt100 / Thermoelement J, K, S
or 4...20 mA / 0...1 V / 0...10 V
• Relay outputs
2 x NO 8(3) A, 250 V AC + 1 x NC
• Other outputs
acoustic alarm (optional)
• Data memory
EEPROM
• Ambient temperature
0 ... +60°C / +32 ... +140°F
• Storage temperature
-30 ... +85°C / -22 ... +185°F
• Air humidity
20 ... 85% (non-condensing)
• Measurement range
according to sensor
• Resolution
0.1°C or 1°F
• Accuracy at + 25 °C
better than 0.5% of the measurement range