beautypg.com

English, 6factory setting – Burkert Type TAT002 User Manual

Page 23

background image

0911 - 21

english

6

FACTORY SETTING

PA

1

Description

Range

Default

PE

2

SET1

Set-value 1

LS1 + US1

0

Pr1

SET2

Set-value 2

LS2 + US2

1

Pr1

HY1

Switch hysterisis 1

dependent on measurement

range

-1

Pr1

Switch hysterisis 2

dependent on measurement

range

-1

Pr1

Ft

Controller type

onF = ON/OFF; Pid = PID

Pid

Pr2

LS1

Lowest set-value 1

Lower measurement range +

SET1

min

Pr2

Lowest set-value 2

Lower measurement range +

SET2

min

Pr2

US1

Largest set-value 1

Upper measurement range +

SET1

max

Pr2

Largest set-value 2

Upper measurement range +

SET2

max

Pr2

S1C

Control effect Output 1

in = inverse; dir = direct

in

Pr2

Control effect Output 2

in = inverse; dir = direct

in

Pr2

ouc

Ac

0...250 sec

0

Pr2

on

Minimum switch-on time

for a relay

0...250 sec

0

Pr2

Minimum waiting time

between two consecutive

activations of the same

load

0...120 min

0

Pr2

Alarm limits are absolute

values or related to the

set-value

rE = relative; Ab = absolute

rE

Pr2

Lower Alarm Limit

(ALC = rE; ALC = Ab)

dependent on measurement

range

10

Pr2

Upper Alarm Limit

(ALC = rE; ALC = Ab)

dependent on measurement

range

10

Pr2

Switch hysterisis for

temperature alarms

dependent on measurement

range

2

Pr2

ALd

Alarm delay time during

the operation

0...999 min

15

Pr2

dAO

0...23.5 h

1.3

Pr2

1

Parameter

2

Programming level

This manual is related to the following products: