English – Burkert Type TAT002 User Manual

Page 24

background image

22 - 0911

english

PA

1

Description

Range

Default

PE

2

So1

Output 1 for sensor error

oFF = open; on = closed

oFF

Pr2

So2

Output 2 for sensor error

oFF = open; on = closed

oFF

Pr2

tbA

Alarm relay can be

acknowledged

no; yES

yES

Pr2

Polarity of the Alarm

relay

CL...oP

oP

Pr2

LCI

3

value

depending on sensor

var.

Pr1

UCI

3

Upper analog display

value

depending on sensor

var.

Pr1

Opb

0

Pr1

rES

Resolution

in = Integer; dEC = 0.1;

cE = 0.01;

irE = large measuring range

in

Pr2

Pb

int

0...999 sec

500

Pr2

dEt

Derivative action time

0...999 sec

30

Pr2

Measurement rate

1...10 sec

2

Pr2

Manual reset

Down scale / Full scale

0

Pr2

Integral band

0...full scale

10

Pr2

cyt

drb

dSi

Dynamic set-value

increase

0...full scale

10

Pr2

Clock time for dyn. set-

value increase

1...999 sec

120

Pr2

UdM

Type TU: °C = °C, °F = °F;

Type AU: 0 = °C, 1 = °F;

2 = RH, 3 = bar, 4 = PS,

5 = without display

var.

Pr1

Type of sensor

Pt = Pt100; J = tcJ; c = tck;

S = tcS; Ptc = PTC;

ntc = NTC; 0.1 = 0...1 V;

10 = 0...10 V; cur = 0...20 mA

var.

Pr1

P3F

1

Parameter

2

Programming level

3

Only for devices with voltage and current input