beautypg.com

Burkert Type 8697 User Manual

Page 8

background image

8

Particularsafetyinstructions

BVS 13 ATEX E104X / E087X

Approval sticker

ATEX marking

IECEx marking

ATEX approval number

IECEx approval number

ii 2G ex ia iic t4 Gb
ii 2d ex ia iiic t135°c db iP64/67

iecex eXAm 13.XXXXX

eXAm 13 AteX XXXXX

ex ia iic t4 Gb
ex ia iiic t135°c db iP64/67

ce0102

ii 2G ex ia iic t4 Gb
ii 2d ex ia iiic t135°c db iP64/67

Degree of protection
Equipment protection level

Ignition degree of protection

Gas group

Temperature class

Marking dust explosion protection

Marking gas explosion protection

Fig. 3: Example approval sticker

4.1.6 Temperature ranges in

explosion-risk areas

Ambient temperature
Type 8697 PX03 (3 GD (tcnA))

0 – + 55 °C

Type 8697 PE99 (2 GD)

0 – + 55 °C

1)

Type 8697 PE51 (2 G with pilot valve) -10 – +55 °C

1)

Type 8697 PE51 (2 G without pilot valve) -20 – +60 °C

4.1.7 Electrical data PE99 and PE51

The device in ignition degree of protection intrinsic safety Ex ia IIC/IIIC
(PE99 and PE51) may be connected only to intrinsically safe electric
circuits.
Explosion group

IIC/IIIC

Category

ia

Temperature class

T4 / 135 °C

1)

The maximum ambient temperature may be restricted by the maximum
allowable input power Pi of the pilot valve (see "Tab. 1: Value pairs input
voltage - input current" on page 9
).

English