Burkert Type 6211 User Manual
Page 5
16
before installation
7.2.
Installation position:
Installation can be in any position.
Preferably: Actuator upright
Prior to installation check pipelines for dirt and, if required,
→
clean.
Dirt filter: To ensure that the solenoid valve functions reliably,
a dirt filter (≤ 500 µm) must be installed in front of the valve
inlet.
installation
7.3.
Hold the device with a suitable tool (open-end wrench)
→
on the housing and screw into the pipeline.
note!
Caution risk of breakage!
Do not use the coil as a lifting arm.
•
Observe direction of flow:
→
The arrow on the housing indicates the direction of flow
(no function in opposite flow direction)!
english
17
Electrical connection of the
7.4.
cable plug
Danger!
Risk of injury due to electrical shock!
Before reaching into the device or the equipment,
•
switch off the power supply and secure to prevent
reactivation!
Observe applicable accident prevention and safety
•
regulations for electrical equipment!
If the protective conductor is not connected, there is a
risk of electric shock!
Always connect protective conductor.
•
Check electrical continuity between coil and housing.
•
max. 0.4 Nm
Authorised cable plug e.g. Type 2507 or
other suitable cable plug in accordance with
DIN ISO 175301-803 Form A
Seal
Electrical connection of the cable plug
Fig. 2:
english
18
Note the voltage and current type as specified on
the rating plate.
Tighten cable plug (for permitted types see data sheet),
→
observing max. torque 0.4 Nm.
Check that seal is fitted correctly.
→
Connect protective conductor and check electrical
→
continuity between coil and housing.
english
19
mainTEnancE,
8.
TrOublEshOOTing
safety instructions
8.1.
Danger!
Risk of injury from high pressure in the equipment!
Before loosening the pipes and valves, turn off the
•
pressure and vent the pipes.
Risk of injury due to electrical shock!
Before reaching into the device or the equipment,
•
switch
off the power supply and secure to prevent reactivation!
Observe applicable accident prevention and safety
•
regulations for electrical equipment!
Warning!
Risk of injury from improper maintenance!
Maintenance may be carried out by authorized techni-
•
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
Secure system from unintentional activation.
•
Following maintenance, ensure a controlled restart.
•