Burkert Type 5282 User Manual
Page 5

11
6.2 Malfunctions
If malfunctions occur, check whether:
→
the device has been installed according to the instructions,
→
the electrical and fluid connections are correct,
→
the device is not damaged,
→
all screws have been tightened,
→
the voltage and pressure have been switched on,
→
the pipelines are clean.
Malfunction
Possible cause
Valve does not switch Short-circuit or coil interrupted
Medium pressure outside the permitted
pressure range
Manual emergency actuation locked
Valve does not close
Internal space of the valve is dirty
Manual emergency actuation locked
7
SPARE PARTS
CAUTION!
Risk of injury and/or damage by the use of incorrect parts!
Incorrect accessories and unsuitable spare parts may cause injuries
and damage the device and the surrounding area.
• Use original accessories and original spare parts from Bürkert only.
7.1 Ordering spare parts
Replacement part sets
Order the spare-part set SET 3 or the pilot control with solenoid coil (com-
plete) by quoting the identification number of the device.
• See replacement part sets “7.2 Exploded drawing”.
• The identification number of the device can be found on the type label.
See also chapter “4.5 Type label”.
english
12
7.2 Exploded drawing
Pilot valve
SET 3
8
TRANSPORT, STORAGE,
DISPOSAL
NOTE!
Transport damages!
Inadequately protected equipment may be damaged during transport.
• During transportation protect the device against wet and dirt in
shock-resistant packaging.
• Avoid exceeding or dropping below the allowable storage
temperature.
Incorrect storage may damage the device.
• Store the device in a dry and dust-free location!
• Storage temperature: -40 °C ... +80 °C
Damage to the environment caused by device components
contaminated with media.
• Observe applicable regulations on disposal and the environment.
• Observe national waste disposal regulations.
→
Dispose of the device and packaging in an environmentally friendly
manner.
english
Type 5282