10 - 2712 big

M

AINTENANCE

AND

S

ERVICING

hsi

lg

ne

Possible malfunctions concerning the actuator are listed in the operatinginstructions for the Top

Control.

Replacing the control cone

Malfunctions

Replacing the control cone:

Knock out the dowel pin with a suitable driver.
Driver diameter Ø

8 mm

Pull off the control cone with the aid of two metal strips of equal
height that are clamped to the left and right of the spindle between
the control cone and the threaded nipple of the actuator. To pull off
the control cone, apply compressed air (approx. 6 bar) to the lower
control connection of the actuator.
Place the new control cone onto the end of the spindle.
Align the bores to each other.

On the fluidic side, the control cone can be replaced in case of wear or damage. For this purpose, the

actuator must be disassembled from the housing.

ATTENTION!

Do not damage the sealing surface or the control

contour!

ATTENTION!

Do

not loosen the screw (SW65) above the threaded nipple!

dowel pin

control

cone

ATTENTION!

Repairs to the actuator may only be carried out in the factory. Contact your Bürkert

branch or our Customer Service directly:

Bürkert Fluid Control Systems

Sales Center

Christian-Bürkert-Str. 13-17

D-76453 Ingelfingen

Tel.: +49 (0) 7940 - 10 91 111

Fax: +49 (0) 7940 - 10 91 448

E-Mail: [email protected]

Disassembly

Remove the electrical and pneumatic supplies from the Top

Control.

Pull off the pneumatic hose between Top

Control and actuator at the

control port of the latter.
Control function A:
Pressurize the lower control port of the actuator with compressed
air (6 bar), so that the control cone is liftet from the valve seat and
is not damaged.
Control function B:
With control function B, no compressed air must be applied for this
purpose.
Remove the actuator in the open valve position by unscrewing the
threaded nipple (SW70) from the housing.

screw

(SW65)

threaded nipple

(SW70)