Intended use

4.2. Sticker for the ex area

achtung: in ex-bereichen darf die oberfläche
nur mit einem feuchten tuch gereinigt werden
caution: in hazardous areas the surface

may only be cleaned with a wet towel

ii 2g c iic t4
ii 2d c t135°c

Warning: not valid when non-ex devices added

Warning: potential electrostatic charging hazard

- see instructions

4.3. Temperature ranges in the ex area

max. ambient

temperature

medium

up to dn 25

above dn 25

T6 85°C

-10 to +45°C

-10 to +55°C

100°C

-10 to +60°C

-10 to +70°C

T4 135°C

-10 to +95°C

-10 to +105°C

10

20

30

40

50

60

70

80

90

100 110 120 130

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

Temperature class T6

Temperature class T5

Temperature class T4

Medium temperature [°C]

Ambient temperature [°C]

Valves
up to
DN 25

Valves
larger
than
DN 25

4.4. Special conditions

To ensure potential equalization, ground the valve body to the pipe
system using an electrically conductive connection.

For use in Ex area zone (gas) 1 and 2,

zone (dust) 21 and 22, applies:

Danger!

danger of explosion caused by electrostatic charge!
In the event of a sudden discharge from electrostatically charged
devices or individuals there is a risk of an explosion in the Ex area.
• Implement suitable measures to ensure that there are no electro-

statically charges in the Ex area.

• Only clean the surface of the device by gently wiping with a

damp or anti-static cloth.

Observe temperature ranges in the Ex area (see “4.3”)!