Flowline LI40-1001 PodView User Manual
Page 13

Rev A
MN204260
13 of 16
GETTING AROUND PODVIEW®
Step Eight
Changing a Pump Set Point: EchoPod® sensor models with relays have (1‐4) channels. If after accessing the
MENU, PUMP appears in the display, then at least (1) relay is configured for pump or valve control. Simplex
pump control has (1) ON and (1) OFF setting. Duplex pump control (2‐pumps) has a third additional LAG
setting. Note: Prior to making any changes, we recommend that you write down all existing set point values.
The example below highlights a duplex pump system in an automatic empty or automatic fill operation with
(1) LAG, (1) ON and (1) OFF set point. Use the following steps to change your simplex or duplex pump control
settings.
Automatic Empty Operation
Automatic Fill Operation
Steps to Change Pump Set Points
1. Hold SELECT for 5 seconds to enter the MENU.
2. Press SELECT when PUMP appears.
3. Press SELECT when the set point (ON, OFF, LAG) you want to
change appears.
4. Press the UP and DOWN buttons to increase or decrease the
set point to the desired value. To scroll faster, hold SELECT
while pressing UP or DOWN.
5. To enter the set point, hold SELECT for 2 seconds.
6. To change another set point, press SELECT when the set
point appears.
7. To exit the MENU, press SELECT when RUN appears.
Tech Tips
Never place a relay set point (ON, OFF, LAG) at the liquid empty or liquid full position. You should have
at least some distance or volume buffer separating them. For example, in a 500 gallon tank, the relay
set points could be placed at ≥ 10 gallons or ≤ 490 gallons.