Number of Pumps

This feature allows you to select the number of pumps or valves used
with EchoPod. This is the setting that activates the control
capabilities of up to two relays. Control relays are often referred to
as Latching relays.

o Switch/Alarms OnlyThe relays will be standard single

point relays (High and/or Low alarms). Relays are non-
latching.

o 1- Pump/Valve – One relay will be configured as a control or

latching relay (relay will have a start level and a separate stop
level). Use this setting to control one pump or valve for
automatic filling or emptying of a tank.

o 2-Pumps/Valves – Two relays are configured as control or

latching relays. Each relay will have a unique start level and
a common stop level. Use this setting to control two pumps
or valves for automatic filling or emptying of a tank.

o 4-20mA Transmitter Only – This setting will disengage all of

the relays. Use this function if you are not using any relays
and using only the 4-20 mA current output.

Note: Right click on any menu that you may have questions on to open the help menu.

Note:
To reset, press the Clear Screen button.