1 heating temperature setting, 2 dhw set temperature, Heating and domestic hot water temperature setting – DE DIETRICH MIT-II-E, MIT-II-H, MIT-EP, MIT-HP and QUADROPAC DUP 500 User Manual
Page 9
9
14/04/2010 - 300015090-001-L
MIT-II - MIT/P - QUADROPAC DUP 500
4 Heating and domestic hot water temperature
setting
4.1 Heating temperature setting
The comfort and reduced temperatures are set separately for each
circuit:
- Select the comfort temperature or the reduced temperature for the
desired circuit by successively pressing key
2%
or
2$
.
- Set the temperature using keys
and
.
The graphic bar displays the heating programme for the
displayed circuit for the current day.
End of setting: Press the AUTO key or after 2 minutes.
* Is displayed if the following 2 conditions are satisfied:
- at least one room sensor is connected on a circuit which is
configured in underfloor heating (FL.HE.),
- cooling mode on.
• In summer mode, when the room temperature measured by the
sensor is higher than the set point ROOM REFR.T., the cooling
mode starts up. The cooling mode shuts down when the room
temperature measured is lower than ROOM REFR.T. -0.5°C.
• In parallel, depending on the outside temperature, automatic
cooling remains on.
4.2 DHW set temperature
- Select the domestic hot water temperature using key
2
and
set the temperature using keys
or
.
If there is no domestic hot water sensor, pressing this key has
no effect.
- End of setting: Press the AUTO key or after 2 minutes.
If DHW consumption is high, increase the domestic hot water
set temperature to 60°C.
2%
Comfort temperature - Cooling
2$
Reduced temperature
2
Domestic hot water temperature
0
2
4
6
8
10
12
14
16
18
20
22
24
A
C000142_02
SUNDAY
-04
Temperature
2
Factory setting
Adjustment range
%
DAY TEMP. A
20 °C
5 to 30 °C
In steps of 0.5°C
ROOM REFR.T. *
25 °C
22 to 30 °C
In steps of 0.5°C
$
NIGHT TEMP. A
16 °C
5 to 30 °C
In steps of 0.5°C
Temperature
Adjustment range
Factory setting
Domestic hot
water
2
10 to 80 °C
In steps of 5°C
55 °C