MIT-II - MIT/P - QUADROPAC DUP 500

H.PRES. FAIL.

x

x

High Pressure fault
Installation malfunction
The PAC has been deactivated
after reaching the high pressure
limit

- Heating water flow rate too low
- Heating circulating pump defective
- Differential valve incorrectly set or incorrectly

dimensioned

- Air in the heating circuit
- Nonreturn valve in the collector open or faulty
- HP pressure switch defective
- Condensor blocked
- Regulator faulty

HOT GAS FAIL.

x

Hot gas fault

The temperature between the primary and the PAC
outlet is too high. (For example: -20°C outside - 50°C at
PAC outlet)
- Heating water flow rate too low
- Heating circulating pump defective
- Differential valve incorrectly set or incorrectly

dimensioned

- Air in the heating circuit
- Nonreturn valve in the collector open or faulty
- HP pressure switch defective
- Condensor blocked
- Regulator faulty

L.PRES. FAIL

x

x

Low Pressure fault
PAC malfunction
The PAC has been deactivated
after reaching the high pressure
limit

- System temperature too low
- Evaporator on PAC air/water frozen
- Heat source production or collector on PAC under-

dimensioned

- Leak in refrigerant circuit
- LP pressure switch defective
- Filter blocked
- Regulator faulty
- Glycol water concentration too weak
- Evaporator on PAC blocked

MOT.PROT.FAIL

x

x

Motor/compressor protection
PAC malfunction
Compressor fault

- defective
- Progressive starter faulty
- Filter blocked
- Electricity consumption too high
- Glycol water concentration too weak (< 25 %)
- Evaporator rusty

FLOW FAIL.

x

x

Flow rate fault (Only with hot
water PACs and heating with 1
compressor)
Installation malfunction

- On NAPO PAC

:

Flow rate on well too low

- Filter blocked
- Absorption well and supply well inverted
- Evaporator on PAC blocked

COMP.FAIL.

x

Fault level: temporary

- Compressor rotation

HP OUT LIMIT

x

Under the lower operating limit
Installation malfunction

- Antifreeze protection 2 time in 2 hours

OUT LIMIT 1

x

Under the lower operating limit -

OUT LIMIT 3

x

Above the upper operating limit -

FAIL. H.P PAC

x

Fault level: Permanent /
temporary

- HP or fin tube battery sensor short circuited

Display

ROE-II

ROE-H

ROE+

ROE+TH

SOLO
NAPO

ROI+

Installation malfunction/HP or

PAC

Meaning / Cause (listed in order of likelihood)

When a fault is displayed followed by AUTO, this disappears automatically after a few minutes. When the fault displayed is followed by
MANU, it is necessary to reset the HP using the reset button (See section 3.1).