3 miscellaneous settings, 4 setting the time and the date - summer time, 7 message – DE DIETRICH MIT-II-E, MIT-II-H, MIT-EP, MIT-HP and QUADROPAC DUP 500 User Manual
Page 16: Message
16
MIT-II - MIT/P - QUADROPAC DUP 500
14/04/2010 - 300015090-001-L
6.3 Miscellaneous settings
1. Use the
J
key to select the paragraph #SETTING.
2. Display the desired parameter using key
I
.
3. Set the value of the parameter by pressing buttons
and
:
`
SUM/WIN: Automatic heating shutdown instruction.
Used to set the outside temperature above which heating will be
shut down.
- The symbol SU appears.
If this parameter is set to NO, the heating is never shut down
automatically.
The cooling mode is activated when the following conditions are
satisfied:
- Parameter REFR.: is set to ON
- Outside temperature > SUM/WIN instruction + SUM/WIN BAND
- The circuit is configured as underfloor heating or convector fan.
Z
See: Technical and installation instructions for MIT.
`
CALIBR. OUT: Outside sensor calibration
Used to correct the outside temperature.
For example
:
Outside temperature measured = 10 °C
Temperature displayed = 11 °C
Set parameter CALIBR. OUT to -1.
Calibration only becomes effective after a few dozen seconds,
and the display is corrected only after this time.
`
ANTIFR. ROOM...: Room antifreeze
Setting the minimum room temperature which is maintained in
the antifreeze mode for each circuit.
This temperature is only checked if a room sensor is connected.
Without a room sensor, this parameter is not displayed and the
set temperature is 6 °C (not adjustable).
`
CALIBR. ROOM...: Room sensor calibration
Used to correct the room temperature display.
For example
:
Room temperature measured = 20 °C
Temperature displayed = 19 °C
Set parameter CALIBR. ROOM... to +1.
When a remote control is connected, this setting must be made
at least 2 hours after the power is turned on, to enable the room
temperature to stabilise.
`
AMB OFFSET...: Room offset - Without room sensor
Is used to set a room offset.
For example:
Set room temperature = 20 °C
Measured temperature = 19 °C
Set parameter AMB OFFSET... to +1.
The setting must be made after the temperatures have
stabilised.
6.4 Setting the time and the date - Summer time
1. Press the
J
key to select the #TIME . DAY menu
2. Display the desired parameter using key
I
.
3. Set the value of the parameter by pressing buttons
and
:
HOURS
MINUTE
DAY
MONTH
DATE
YEAR
SUM. TIME: AUTO (Factory setting) - MANU
The control unit is programmed to switch automatically to
summer time on the last Sunday in March and back to winter
time on the last Sunday in October.
When the setting is on "manual", the automatic change does not
take place.
7 Message
Message
Probable causes
Action
SHOW REM. CTRL The message SHOW REM. CTRL signals the presence of an
override on a remote control
To cancel the overrides on all remote controls, press the AUTO
key for 5 seconds.