beautypg.com

DE DIETRICH MIT-II-E, MIT-II-H, MIT-EP, MIT-HP and QUADROPAC DUP 500 User Manual

Page 14

background image

14

MIT-II - MIT/P - QUADROPAC DUP 500

14/04/2010 - 300015090-001-L

#SETTING

x

x

x

x

x

x

The parameters are set using keys

or

.

Z

See also: Miscellaneous settings.

-

-

CONTRAST DISP.

x

x

x

x

x

x

Adjusting the display contrast

-

-

BACK LIGHT

x

x

x

x

x

x

ON: The lighting is permanent if the circuit is in
Daytime period

.

If the circuit displayed is in a

Night period, the backlighting is ECO.

ON

ON, ECO

or OFF

ECO: If the circuit displayed is in Nighttime
period, the lighting is on for 2 minutes if a key on
the keyboard is pressed.
OFF: The display is never lit

SUM/WIN

x

x

x

x

x

x

Summer/winter setting

22 °C

15 to

30 °C -

OFF

CALIBR. OUT

x

x

x

x

x

x

Outside sensor calibration

0.0

-5.0 to

+5.0 K

CALIBR. ROOM A *

x

x

x

x

x

x

Calibration of the room sensor on circuit A

0.0

-5.0 to

+5.0 K

OFFSET ROOM A *

x

x

x

x

x

x

Room offset on circuit A

0.0

-5.0 to

+5.0 K

OFFSET ROOM B *

x

x

x

x

x

x

Room offset on circuit B

0.0

-5.0 to

+5.0 K

ANTIFR. ROOM A *

x

x

x

x

x

x

Room temperature antifreeze activation on circuit
A

6 °C

0.5 to

20 °C

CALIBR. ROOM B *

x

x

x

x

x

x

Calibration of the room temperature sensor on
circuit B

0.0

-5.0 to

+5.0 K

ANTIFR. ROOM B *

x

x

x

x

x

x

Room temperature at which the antifreeze mode
is activated on circuit B

6 °C

0.5 to

20 °C

#TIME . DAY

x

x

x

x

x

x

The parameters are set using keys

or

.

Z

See also: Setting the time and the date

- Summer time.

-

-

HOURS

x

x

x

x

x

x

MINUTE

x

x

x

x

x

x

DAY

x

x

x

x

x

x

MONTH

x

x

x

x

x

x

DATE

x

x

x

x

x

x

YEAR

x

x

x

x

x

x

SUM. TIME:

x

x

x

x

x

x

AUTO: automatic switch to summer time on the
last Sunday in March and back to winter time on
the last Sunday in October.
MANU: for countries where the time change is
done on other dates or is not in use.

AUTO

AUTO or

MANU

Display

ROE-II ROE-H ROE+ ROE+TH SOLO,

NAPO

ROI+

Parameter set

Factory

setting

Adjustme

nt range

* The line or title is only displayed for the options, circuits or sensors actually connected

.