coupled pumps and is flushed and vented to

the suction on close coupled pumps.

The split-coupled pump is flushed from the

pump discharge because the mechanical seal

chamber is isolated from the liquid in the

pump by a throttle bushing. Because the seal

chamber is isolated, seal environmental

controls such as filters and separators, when

installed in the split-coupled flush line are

very effective, as only the seal chamber

needs cleansing, and will prolong seal life in

HVAC systems.

Do not run the pump unless properly filled

with water as the mechanical seals need a

film of liquid between the faces for proper

operation.

Mechanical seals may ‘weep’ slightly at

start-up. Allow the pump to continue

operating for several hours and the

mechanical seal to ‘seat’ properly prior to

calling for service personnel.

System Cleanliness

Before starting the pump the system must be

thoroughly cleaned, flushed and drained and

replenished with clean liquid.

Welding slag and other foreign materials,

“Stop Leak” and cleaning compounds and

improper or excessive water treatment are

all detrimental to the pump internals and

sealing arrangement.

Proper operation cannot be guaranteed if the

above conditions are not adhered to.

Note:

Particular care must be taken to check the

following before the pump is put into

operation:

1. Pump primed?

2. Rotation OK?

3. Lubrication OK?

4. Pipe work properly supported?

5. Voltage supply OK?

6. Overload protection OK?

7. Is the system clean?

8. Is the area around the pump clean?

Warranty

Does not cover any damages to the

equipment resulting from failure to observe

the above precautions.

Double Check Prior to Startup.