AAON LC-054 User Manual
Page 22

22
The system is undercharged if the superheat
is too high and the sub-cooling is too low.
Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.
If the sub-cooling is correct and the
superheat is too high, the TXV may need
adjustment to correct the superheat.
Table 3 - R-410A Refrigerant Temperature-Pressure Chart
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
20
78.3
47
134.7
74
213.7
101 321.0
128 463.2
21
80.0
48
137.2
75
217.1
102 325.6
129 469.3
22
81.8
49
139.7
76
220.6
103 330.2
130 475.4
23
83.6
50
142.2
77
224.1
104 334.9
131 481.6
24
85.4
51
144.8
78
227.7
105 339.6
132 487.8
25
87.2
52
147.4
79
231.3
106 344.4
133 494.1
26
89.1
53
150.1
80
234.9
107 349.3
134 500.5
27
91.0
54
152.8
81
238.6
108 354.2
135 506.9
28
92.9
55
155.5
82
242.3
109 359.1
136 513.4
29
94.9
56
158.2
83
246.0
110 364.1
137 520.0
30
96.8
57
161.0
84
249.8
111 369.1
138 526.6
31
98.8
58
163.8
85
253.7
112 374.2
139 533.3
32
100.9
59
166.7
86
257.5
113 379.4
140 540.1
33
102.9
60
169.6
87
261.4
114 384.6
141 547.0
34
105.0
61
172.5
88
265.4
115 389.9
142 553.9
35
107.1
62
175.4
89
269.4
116 395.2
143 560.9
36
109.2
63
178.4
90
273.5
117 400.5
144 567.9
37
111.4
64
181.5
91
277.6
118 405.9
145 575.1
38
113.6
65
184.5
92
281.7
119 411.4
146 582.3
39
115.8
66
187.6
93
285.9
120 416.9
147 589.6
40
118.1
67
190.7
94
290.1
121 422.5
148 596.9
41
120.3
68
193.9
95
294.4
122 428.2
149 604.4
42
122.7
69
197.1
96
298.7
123 433.9
150 611.9
43
125.0
70
200.4
97
303.0
124 439.6
44
127.4
71
203.6
98
307.5
125 445.4
45
129.8
72
207.0
99
311.9
126 451.3
46
132.2
73
210.3
100 316.4
127 457.3