Delta Controls DPR-2000 User Manual
Page 31
![background image](/manuals/326832/31/background.png)
A
29 IOM-DPCDPR-A: FEB 2014
10.2.6. Local Menu, error reports.
During executing in Local Menu some functions, LCD2 announcement can be displayed on the screen.
The error displaying evidences about no realization of command of Local Menu.
The shortened description of errors announcements is showed below.
ERR_L07
[in_write_protected_mode]. Error will ensue out when we try to change setting in Local
Menu, but transmitter is protected before recording. To to make the change of setting with
Local Menu using, transmitter has to have the included service of Local Menu as well as
switched off protection before record. These parameters modification is possible by using
KAP -
03 communicator, “D-SOFT” program or software using library EDDL.
default setting:
Local Menu service
switched on
protection before record
switched off
ERR_L09
[applied_process_too_high]. Error will ensue out when given parameter (pressure)
exceed admissible value. Zeroing or the range setting verifying is necessary.
ERR_L10
[applied_process_too_low]. Error will ensue out when given parameter (pressure)
will too low. Zeroing or the range setting verifying is necessary.
ERR_L14
[span_too_small]. Error will ensue out when in result of setting range executing change
the width of the range will be smaller than admissible.
ERR_L16
[acces_restricted]. Error will ensue out when the service of Local Menu is switched off,
and the user tries to call out the Menu Local service. You should switch on the service of
Local Menu with the KAP-
03 communicator, “D-SOFT” program, or software using library
EDDL.
Warning!, ERR_L16 announcement can be displayed as well by zeroing attempt of the
absolute transmitter .
WNG_L14
[WARNING!, new Lower Range Value Pushed !] Error will ensue out when the end of
range set ( the URV) change will cause the change of the range set beginning (LRV).
10.2.7. Remote configuration
Remote configuration is possible with KAP-XX communicator or PC software. Measuring circuit should be in
accordance with the fig. 2.