Delta Controls DPR-2000 User Manual
Page 30

A
28 IOM-DPCDPR-A: FEB 2014
Descriptions
EXIT
return from the local Menu to the normal operation of the transmitter
UNIT
menu process variable units. Options:
IN_H2O inches of water at a temperature of 68 ° Fahrenheit
IN_HG
inches of mercury at a temperature of 68 ° Fahrenheit
FT_H2O foot of water a temperature of 68 ° Fahrenheit
MM_H2O mm of water at a temperature of 68 ° Fahrenheit
MM_HG mm of mercury at 0 ° C
PSI
BAR
bar
MBAR
millibar
G/SQCM grams per square centimetres
KG/SQCM kilogram per square centimetres, technical atmosphere
PA
pascal
KPA
kilopascal
TORR
tor (mm Hg)
ATM
physical atmosphere
M_H2O meter of water at 4 ° C
MPA
megapascal
INH2O@4 inch of water at a temperature of 4 ° C
MMH2O@4 mm of water at 4 ° C
DAMPIN
menu damping of process variable [s]. You can choose 0,2,5,10,30,60 [s]
TRANSF
type of current output characteristic Menu. Options:
LINEAR linear
SQRT
square root
SPECIA us
er’s special
SQUARE square
%SQRT
menu of, point insensitivity of square root characteristics. To select 0%, 0.2%, 0.4%, 0.6%,
0.8%, 1.0% range
PVZERO
pressure zeroing
.
SETURV
setting the upper range value by the done pressure
SETLRV
setting the lower range of values set by the done pressure
RESET
reboot your transmitter
LCD1VR
assigning a process variable to LCD1. Options:
CURREN current in the line in [mA]
PERCEN percent of the set range - controling in%
LCD2VR
assigning a process variable to LCD2. Options:
PRESS pressure value in units UNIT
USER
pressure value in user’s units
Scaling of the user range and record of the user units can be made using a computer or
communicator, see → HART command No. 244.245
SENS_T
sensor temperature value in the pressure header in °
CPU_T
CPU electronics board temperature value - in º C
LCD2DP
setting the decimal point position on LCD2. Options:
XXXXX·
XXXX·X
XXX·XX
XX·XXX
X·XXXX
In a situation where the value provided to display on the display LCD2 can not be
displayed properly due to the position of the decimal point, this is indicated by displaying
the four flashing dots • • • •. In this case, you must enter to the local menu setting and
move the decimal point respectively to the right.
FACTOR
back to factory settings (removing of current and pressure calibrations).
MID_WP
blocking records / change the parameters associated with transmitter metrology
ON
switch on blocking
OFF
switch of blocking