11 IOM-DPCDPR-A: FEB 2014

5.1.2.3. Climatic immunity: dry heat, cold, humidity, salt mist:

Dry heat:
EN 60068-2-2, test B; T = 70

0

C, RH = max 55%

Cold :
EN 60068-2-1, test A; T = -25

0

C,

Damp heat cycle:
EN 60068-2-30, test D ; (T = 55

0

C, RH = min95%, 24h)x2

Salt mist:
EN 60068-2-52; (spraying: 2h duration, T = 25

0

C, storage in damp chamber: 7 days, T = 40

0

C, RH = 93%)x4,

28days total

5.1.2.4. Mechanical immunity

Shocks:
EN 60068-2-27, 50g/11ms

Vibrations:
EN 60068-2-

6, test Fc; up to 1,6mm for 2 … 25Hz, up to 4g for 25 … 100Hz

5.1.3.1. Insulation Resistance

>100 MΩ @110V transmitters with gas arresters
>100 MΩ @750V DC transmitters without gas arresters

5.1.3.2. High Voltage Test

500V AC, or 750V DC, 1min, transmitters without gas arresters
75V AC, or 110V DC, 1min, transmitters with gas arresters

5.1.4. Enclosure ingress protection

EN 60529, IP 66,67

5.1.5. DPC..., DPR... Construction materials

Diaphragm seal for DPC...

Stainless steel 316L (00H17N14M2) or Hastelloy C276

Diaphragm seal for DPR...

Stainless steel 316L (00H17N14M2) or Hastelloy C276

Sensing module

Stainless steel 316L (00H17N14M2)

Liquid filling the interior the sensing module Silicone oil, chemically inactive liquid for measurement of

oxygen uses.

Connectors for DPC...

Stainless steel 316L (00H17N14M2) or

Hastelloy C276 only for P, GP, CM30x2

C-type vented covers and connectors for DPR.. Stainless steel 316L (00H17N14M2)
Electronics casing

High pressure cast of aluminium alloy, lacquered with

chemical-resistant oxide enamel, colour yellow (RAL 1003).