The (TRIMxxx) functions are used to trim the Lower and Upper Range Values of the analogue to
digital converter (ADC) to an accurately generated, external pressure standard. This is used if the
instrument is found to differ from the site standard, for whatever reason. The command can also
be used to increase the measurement accuracy of a turned down instrument.

23

{HIT SAVE} will be displayed, there are two choices :-

[SELECT] or [CHANGE]

To abort and return to the {TRIM LRV} menu

[[SELECT]]

Press and hold for two seconds to store the ADC offset value,
{SAVED} will be displayed to show that the command is successful.

{TRIM URV}[SELECT]

The URV may be trimmed to increase the accuracy of the transmitter when using large
turndowns. Apply a pressure equal to the LRV pressure. NOTE:- the accuracy of the reference
pressure should be 3 - 5 times better than the instrument.

{HIT SAVE} will be displayed, there are two choices :-

[SELECT] or[CHANGE]

To abort and return to the {TRIM URV} menu.

[[SELECT]]

Press and hold to store the ADC offset value, {SAVED} will be
displayed to show that the command is successful.

Commands and HART Numbers used by 2HT

Number Class

Local

Description

135

D

1 Restore Factory Defaults

148

D

V View Trim settings

149

D

2 Set PV Trim Span

151

D

2 Set Password Access for D-CAL

152

D

V View Model Number

COMMANDS

U Universal

C Common

D Device Specific

LOCAL ACCESS

M Monitor

V View

(D-CAL)

1 Access Level 1

2

Access Level 2

HART Commands

These commands are not supported by the transmitter, but will be decoded when the
SHOWHART command is enabled.

Number Class

Description

33

C

Read Transmitter Variables

39

C

EEprom Control

50

C

Read Dynamic Variable Assignments

51

C

Write Dynamic Variables Assignments

52

C

Set Transmitter Variable Zero

54

C

Read Transmitter Variable Information

55

C

Write Transmitter Variable Damping Value

56

C

Write Transmitter Variable Sensor Serial Number

57

C

Read Unit Tag, Descriptor, Date

58

C

Write Unit Tag, Descriptor, Date

59

C

Write Number of response preambles

108

C

Write Burst Mode Command Number

109

C

Burst Mode Control

110

C

Read All Dynamic Variables

8

{TRIM LRV}[SELECT]

Apply a pressure equal to the LRV pressure (usually, but not necessarily zero!!) to the
instrument, and allowed to settle. NOTE:- the accuracy of the reference pressure should be 3 -
5 times better than the instrument.