Delta Controls 2HTDCAL User Manual
Page 12
The access restrictions apply to local configuration only. It is assumed that remote access, via
a portable HART® configurator on a host computer, is adequately access-protected.
11
MONITOR and VIEW
Monitor mode is the default
of the display, it shows prime
variable, loop current and sensor
temperature. Prime variable is always
displayed, cycling between value and
engineering units, this is to allow
engineering units to be shown
without scrolling the display. It is quite
normal for the D-Cal unit to change its
scroll and cycle speed aid clarity at
lower temperatures.
To gain access to a
restricted level the following steps
should be performed.
{--> 0***} With '0' flashing.
Use the select and change keys to
enter the code number. When the
last digit is selected a decision is
made, if the number is correct the
menu level is entered, other wise the
menu will abort to {ACCESS 1}
If the wrong number is entered
access will be denied.
TRIM 4mA
TRIM 20mA
ESCA PE
ACCESS 2
ESCA PE
ESCA PE
PASSWORD
ACCESS 1
ESCA PE
OUTPUT
FIX LOOP
TRIM LOOP
% OUTPUT
VIEW
ACCESS 1
ACCESS 2
INPUT
TRIM LRV
TRIM URV
ZERO KEY
SPAN KEY
ESCA PE
ACCESS 2
MONITOR PV
LOOP CURRENT
DISPLAY
SENSOR TEMP
{ACCESS 1}
20
{TAG}[SELECT]
An eight character alphanumeric field for identification e.g. {TANK6} {LEVEL9}
The tag is displayed on screen, there are two options :-
[SELECT] To abort displayed tag and return to the TRANSMTR menu.
[CHANGE] Used to edit the display. See page 5 ' Display and Edit '
{MESSAGE}[SELECT]
A 32 character alphanumeric field for any information set by site practice e.g..
{CHECKED BY SIMON 29 02 92} or {HIGH PRESSURE SERVICE}
The message is displayed on screen, there are two options :-
[SELECT] To abort displayed message and return to the TRANSMTR menu.
[CHANGE] Used to edit the display. See page 5 ' Display and Edit '
{DESCRIPT}[SELECT]
A 16 character alphanumeric field for additional identification of the transmitter
e.g.. {TANK 6} {LEVEL 9} {UNIT 27} etc.
The Description is displayed on screen, there are two options :-
[SELECT] To abort displayed message and return to the TRANSMTR
menu.
{DATE}[SELECT]
The date may be the next calibration day, last re-zeroed, according to site practice.
The date is entered in the form DD MM YY
The information is sent digitally in the form MM DD YY.
The date is displayed on screen, there are two options :-
[SELECT] To abort displayed message and return to the TRANSMTR menu.
[CHANGE] Used to edit the display. See page 5 ' Display and Edit '
RESTRICTED ACCESS