beautypg.com

Jw s r – DE-STA-CO VARI-PAK DC CONTROL User Manual

Page 14

background image

12

E. +24 VDC SUPPLY – The +24V terminal provides a nominal

1

24 VDC @ 12 mA output for

use with an external load such as one solid-state 3-wire proximity switch.

F. Common “COM” — This terminal is referenced to all logic signals (RUN, JOG, STOP)

through the Return (“RTN”) terminal. The control is factory supplied with jumper “JR” in
the “F” position which connects the “RTN” and “COM” terminals together.

Note: Control

will not operate unless jumper “JR” is in the “F” position.

VII. APPLICATION WIRING DIAGRAMS

Example 1: Solid-state switching devices, such as NPN transistors or proximity switches,
may be used for logic commands if they meet the following criteria:

TABLE 6 – JUMPER “JW” OPERATION

*See section IV, items 1-4, on page 9.

COM

RTN

RTN

COM

OPEN TO

"F" "O"

"JR"

STOP

"JR"

*

"O"

"F"

FIGURE 11 – JUMPER “JR” OPERATION

Jumper “JR” in “F” position (factory setting)
connects “RTN” to “COM”

Jumper “JR” in “O” position opens the
“RTN” to “COM” circuit allowing the use of
an external disable contact. This will not
stop the indexer in run mode.

1

Output voltage provided can vary between 20 and 24 Volts DC.

Jumper “JW” Setting

Description

Circuit

Operation

JW

S

R

“Run” has priority
over “Stop.” Control
will run even if stop
contact is open. Use
this setting for “Cycle
on Demand” opera-
tion.

RUN

JOG

STP

RTN

STOP

START

*

When start contact is
made, control will
run with stop open.
If stop is closed and
then reopened, con-
trol will stop.

JW

S

R

“Stop” has priority
over “Run.” Control
will run only when
stop contact is
closed.

RUN

JOG

STP

RTN

STOP

*

START

When start contact is
made, stop contact
must be closed for
control to run.

Factory setting