Technical data

5

Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1

Operation instructions

AUMA NORM

Multi-turn actuators AUMA NORM require electric controls. AUMA offers the controls AUMA MATIC AM or AUMATIC AC for the
sizes SA(R) 07.1 - SA(R) 16.1. These can also easily be mounted to the actuator at a later date.

Features and functions

Type of duty

1)

Standard:

SA

Short time duty S2 - 15 min

SAR

Intermittent duty S4 - 25 %

Option:

SA

Short time duty S2 - 30 min

SAR

Intermittent duty S4 -50 %
Intermittent duty S5 - 25 %

Motors

Standard:

3-ph AC asynchronous motor, type IM B9 according to IEC 34

Options:

1-ph AC motor, type IM B14 according to IEC 34
DC shunt motor, type IM B14 according to IEC 34
DC compound motor, type IM B14 according to IEC 34
Special motors

Insulation class

Standard:

F, tropicalized

Option:

H, tropicalized

Motor protection

Standard:

Thermoswitches (NC)

Option:

PTC thermistors (according to DIN 44082)

Supply voltage

Refer to motor nameplate

Self-locking

yes; for output speeds from 4,8 to 108 rpm and from size SA 35.1 for output speeds from 4,8 to 26 rpm

Limit switching

Counter gear mechanism for end positions CLOSED and OPEN
for 1 to 500 turns per stroke (optional for 1 to 5,000 turns per stroke)
Standard:

Tandem switch (2 NC and 2 NO) for each end position; switches galvanically isolated

Options:

Single switch (1 NC and 1 NO) for each end position
Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated
Intermediate position switch (DUO limit switching)

Torque switching

adjustable torque switching for direction OPEN and CLOSE
Standard:

Single switch (1 NC and 1 NO) for each direction

Options:

Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolated

Non-intrusive setting
(option)

Magnetic limit and torque transmitter MWG for the sizes SA 07.1 – SA 48.1
(only possible in combination with actuator controls AUMATIC)
for 1 to 500 turns per stroke or for 10 to 5,000 turns per stroke

Position feedback signal,
analogue (options)

Potentiometer or 0/4 – 20 mA
For further details see separate data sheet

Torque feedback signal,
analogue (option)

Only in combination with magnetic limit and torque transmitter MWG and actuator controls
AUMATIC

Mechanical position
indicator (option)

Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED

Running indication (option)

Blinker transmitter

Heater in switch
compartment

Standard:

self-regulating PTC heater, 5 – 20 W, 110 – 250 V DC/AC

Options:

24 – 48 V DC/AC or 380 – 400 V AC

A resistance type heater (5 W, 24 V DC) is installed in the actuator in combination with the actuator
controls AUMA MATIC or AUMATIC.

Motor heater (option)

SA(R) 07.1 – 10.1:

12.5 W

SA(R) 14.1 – 16.1:

25 W

SA(R) 25.1 – 30.1:

50 W

SA 35.1 – 48.1:

50 W

Manual operation

Manual drive for setting and emergency operation, handwheel does not rotate during electrical
operation.
Option:

Handwheel lockable

Electrical connections

Standard:

SA(R) 07.1 – 16.1:

AUMA plug/socket connector with screw type connection,

SA(R) 25.1 – 48.1: Control connections on AUMA plug/socket connector,

motor connection via terminals

Option:

for special motors:

Motor connection directly via terminal board at the motor

Threads for cable glands

Standard:

NPT-threads

Options:

Pg-threads, G-threads

Terminal plan

Terminal plan according to commission number included in delivery

1) Based on 68 °F ambient temperature and at an average load with running torque according to Technical data SA(R).