9 limit and torque switches, Limit switches 13, Tandem switches 13 – AUMA Electric multi-turn actuators SA 07.1 - 48.1_SAR 07.1 - 30.1 NORM User Manual
Page 13: Limit and torque switches, Fitting of the cover

7.9
Limit and torque switches
Only the same potential can be switched on the two circuits (NC/NO contact) of a
limit or torque switch. If different potentials are to be switched simultaneously,
tandem switches are required.
To ensure correct actuator indications, the leading contacts of the tandem switches
must be used for that purpose and the lagging contacts for motor switching off.
7.10 Fitting of the cover
After connection:
.
Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it with
screws (51.01).
.
Clean sealing faces at the plug cover and the housing.
.
Check whether O-ring is in good condition.
.
Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
.
Replace plug cover (50.0) and fasten bolts (50.01) evenly crosswise.
.
Fasten conduit connections with the specified torque to ensure the required
enclosure protection.
13
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions
AUMA NORM
Mechanical
lifetime = 2 x 10
6
starts
Type of current
Switch rating I
max
30 V
125 V
250 V
1-phase AC
(ind. load) cos phi = 0,8
5 A
5 A
5 A
DC
(resistive load)
2 A
0,5 A
0.4 A
with gold plated
contacts
min. 5 V, max. 50 V
Current
min. 4 mA, max. 400 mA
Table 5: Technical data for limit and torque switches
NO
NC
NC
NO
RD
BK
RD
BK
BK
2
RD 2
BK
RD
BK
2
RD 2
BK
RD
TSC 1 / TSO 1
LSC 1 / LSO 1
TSC / TSO
LSC / LSO
DSR 1 / DÖL 1
WSR 1 / WÖL 1
DSR / DÖL
WSR / WÖL
Figure G-5
II
Tandem switch
SPDT
DPDT
I
Single switch