Setting the limit switching, 1 setting the end position closed (black section), 2 setting the end position open (white section) – AUMA Electric multi-turn actuators SA 07.1 - 48.1_SAR 07.1 - 30.1 NORM User Manual
Page 15: 3 checking the limit switches, Limit switching 15,16, Setting the end position closed (black section), Setting the end position open (white section), Checking the limit switches

9.
Setting the limit switching
9.1
Setting the end position CLOSED (black section)
.
Turn handwheel clockwise until valve is closed.
.
After having reached the end position, turn back handwheel by approximately ½
a turn (overrun). During test run, check overrun and, if necessary, correct setting
of the limit switching.
.
Press down
and turn setting spindle A (figure K-1) with a flat blade
screw driver in direction of arrow, thereby observe pointer B.
While a ratchet is felt and heard, the pointer B moves 90° every time.
When pointer B is 90° from mark C, continue turning slowly. When pointer B has
reached the mark C, stop turning and release setting spindle. If you override the
tripping point inadvertently (ratchet is heard after the pointer has rotated),
continue turning the setting spindle in the same direction and repeat setting
process.
9.2
Setting the end position OPEN (white section)
.
Turn handwheel counterclockwise until valve is open, then turn back by
approximately ½ a turn.
.
Press down
and turn setting spindle D (figure K-1) with a flat blade screw driver
in direction of arrow, thereby observe pointer E.
While a ratchet is felt and heard, the pointer E moves 90° every time.
When pointer E is 90° from mark F, continue turning slowly. When pointer E has
reached the mark F, stop turning and release setting spindle. If you override the
tripping point inadvertently (ratchet is heard after the pointer has rotated),
continue turning the setting spindle in the same direction and repeat setting
process.
9.3
Checking the limit switches
The red test buttons T and P (figure K-1) are used for manual operation of the limit
switches.
.
Turning T in direction of the arrow LSC (WSR) triggers limit switch CLOSED.
.
Turning P in direction of the arrow LSO (WÖL) triggers limit switch OPEN.
15
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions
AUMA NORM
Figure K-1: Control unit
A
T
B
C
D
P
E
F