14.
Setting the electronic position transmitter RWG (option)
– For remote indication or external controls –
After mounting the multi-turn actuator to the valve, check setting by measuring the
output current (see sections 14.1 or 14.2) and re-adjust, if necessary.
The position transmitter board (figure P-1) is located under the cover plate
(figure P-2).
20
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM
Operation instructions
Terminal plans
KMS TP_ _ 4 / _ _ _
3- or 4-wire system
KMS TP _ 4 _ / _ _ _
KMS TP _ 5 _ / _ _ _
2-wire system
Output current
I
a
0 – 20 mA, 4 – 20 mA
4 – 20 mA
Power supply
U
v
24 V DC, ± 15 %
regulated
14 V DC + (I x R
B
),
max. 30 V
max. input
current
I
24 mA at 20 mA
output current
20 mA
max. load
R
B
600
Ω
(Uv - 14 V) /20 mA
Table 7: Technical data RWG 4020
Figure P-1: Position transmitter board