beautypg.com

Electronic position transmitter rwg 20, Position transmitter rwg 20 – AUMA Electric multi-turn actuators SA 07.1 - 48.1_SAR 07.1 - 30.1 NORM User Manual

Page 20

background image

14.

Setting the electronic position transmitter RWG (option)

– For remote indication or external controls –

After mounting the multi-turn actuator to the valve, check setting by measuring the
output current (see sections 14.1 or 14.2) and re-adjust, if necessary.

The position transmitter board (figure P-1) is located under the cover plate
(figure P-2).

20

Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM

Operation instructions

Terminal plans

KMS TP_ _ 4 / _ _ _

3- or 4-wire system

KMS TP _ 4 _ / _ _ _
KMS TP _ 5 _ / _ _ _

2-wire system

Output current

I

a

0 – 20 mA, 4 – 20 mA

4 – 20 mA

Power supply

U

v

24 V DC, ± 15 %

regulated

14 V DC + (I x R

B

),

max. 30 V

max. input
current

I

24 mA at 20 mA

output current

20 mA

max. load

R

B

600

Ω

(Uv - 14 V) /20 mA

Table 7: Technical data RWG 4020

Figure P-1: Position transmitter board