Dcs series : product specifications, Single phase ac input – Atec Sorensen-DCS Series User Manual
Page 2
![background image](/manuals/319952/2/background.png)
www.ProgrammablePower.com
Common
Meter Accuracy
1% of full scale + 1 count
Max. Voltage Differential from Output to
Safety Ground
150 VDC
Remote Start/Stop and Interlock
TTL compatible input or 12-250 VAC (12-130 VDC) or a contact closure
Cooling
Internal fan, over temperature shutdown if internal heat sink exceeds set temperature
Remote Sense
The maximum allowed sense line drop is 4V per line (2V on the DCS 8/10V 1 kW/1.2 kW models and 1V/line for all
3 kW models). Line drop subtracts from the maximum available output voltage at full rated power.
Remote Programming
Enabled via external jumper on rear panel connector J3
Overvoltage Protection
Crowbar type adjustable from 5-110% of rated output using front panel control (local or remote program selectable via J3 jumper)
Remote Analog Programming Linearity
±1%
Accuracy
±5%
Regulatory
Certified to UL/CSA 61010 and IEC/EN 61010-1 CE. Compliant (LVD and EMC directive)
Input
1 kW
1.2 kW
3 kW
Voltage Ranges
200-250 VAC / 100-132 VAC
200-250 VAC / 100-132 VAC
190-250 VAC / 200-250 VAC
Phases
Single Phase
Single Phase
Three Phase / Single Phase * (See Below)
Current
8A typical, 47-63 Hz
15A typical, 47-63 Hz
9A typical, 47-63 Hz
18A typical, 47-63 Hz
190-250 VAC, three phase,
14A, 47-63Hz. * (See Below)
User configurable for: 200-250VAC, single-phase operation, 20A,
47- 63Hz.
* See the modified operation curve below.
Output
Stability
±0.05% of maximum voltage or current over 8 hours after 30 minute warm-up time at fixed line, load and temperature
Line Regulation
For input voltage variation over the AC input voltage range, with constant rated load.
Load Regulation
For 0-100% load variation, with constant nominal line voltage.
Voltage Resolution
0.02%
Transient Response
Typically recovers in 500 μs (1 & 1.2 kW) or 1ms (3k W) to 1% of steady-state output voltage
(within 1% of Vmax) for 70-100% or 100-70% load change.
DCS Series : Product Specifications
Output : Voltage and Current
1 kW Model
Voltage
Current
1.2 kW Model
Voltage
Current
3 kW Model
Voltage
Current
DCS 8-125E
0-8
0-125
DCS 8-140E
0-8
0-140
DCS 8-350E
0-8
0-350
DCS 10-100E
0-10
0-100
DCS 10-120E
0-10
0-120
DCS 12-250E
0-12
0-250
DCS 20-50E
0-20
0-50
DCS 20-60E
0-20
0-60
DCS 20-150E
0-20
0-150
DCS 33-33E
0-33
0-33
DCS 33-36E
0-33
0-36
DCS 40-75E
0-40
0-75
DCS 40-25E
0-40
0-25
DCS 40-30E
0-40
0-30
DCS 55-55E
0-55
0-55
DCS 50-20E
0-50
0-20
DCS 50-24E
0-50
0-24
DCS 60-50E
0-60
0-50
DCS 60-18E
0-60
0-18
DCS 60-20E
0-60
0-20
DCS 80-37E
0-80
0-37
DCS 80-13E
0-80
0-13
DCS 80-15E
0-80
0-15
DCS 150-20E
0-150
0-20
DCS 100-10E
0-100
0-10
DCS 100-12E
0-100
0-12
DCS 150-7E
0-150
0-7
DCS 150-8E
0-150
0-8
DCS 300-3.5E
0-300
0-3.5
DCS 300-4E
0-300
0-4
DCS 600-1.7E
0-600
0-1.7
Modified Operation Curve for DCS Series 3 kW
Voltage
Rated Current
Single Phase AC Input
Rated V
oltage
Curr
ent
2.5kW
44